# Ampacity Chart

Read the conductor material, size and temperature column\. Verify the applicable edition and termination limits before comparing the adjusted ampacity with the load\. A worksheet may illustrate the math, but the result still depends on inputs such as ambient temperature and the conductors sharing the raceway\.

This is corrected insulation ampacity\. Check the terminal and overcurrent protection limits separately\.

NEC 2023 Table 310\.16 base ampacity in amperes

Size

Cu 60 °C

Cu 75 °C

Cu 90 °C

Al 60 °C

Al 75 °C

Al 90 °C

14 AWG

15

20

25

—

—

—

12 AWG

20

25

30

15

20

25

10 AWG

30

35

40

25

30

35

8 AWG

40

50

55

35

40

45

6 AWG

55

65

75

40

50

55

4 AWG

70

85

95

55

65

75

3 AWG

85

100

115

65

75

85

2 AWG

95

115

130

75

90

100

1 AWG

110

130

145

85

100

115

1/0 AWG

125

150

170

100

120

135

2/0 AWG

145

175

195

115

135

150

3/0 AWG

165

200

225

130

155

175

4/0 AWG

195

230

260

150

180

205

250 kcmil

215

255

290

170

205

230

300 kcmil

240

285

320

195

230

260

350 kcmil

260

310

350

210

250

280

400 kcmil

280

335

380

225

270

305

500 kcmil

320

380

430

260

310

350

## Worked examples

1. 6 AWG copper, 90 °C insulation, 40 °C ambient and six current\-carrying conductors gives 54\.60 A \(75 × 0\.91 × 0\.80\)\.
2. 2 AWG aluminum, 75 °C insulation, 30 °C ambient and three current\-carrying conductors gives 90\.00 A\.

## How the calculation works

Multiply the NEC 2023 Table 310\.16 base ampacity by the ambient factor in Table 310\.15\(B\)\(1\) and the conductor\-count factor in Table 310\.15\(C\)\(1\)\. The base table assumes 30 °C ambient and three or fewer current\-carrying conductors\. Verify termination ratings, small\-conductor protection limits, and whether the general adjustment factors apply to the installation\.

## Frequently asked questions

What is the ampacity of 12 AWG wire?

Find 12 AWG in the chart and select the conductor material and temperature column\. The base value is only a starting point\. Ambient temperature, conductor count, terminations and overcurrent protection can limit the usable value\.

Is thicker wire always better?

Larger wire generally has lower resistance and can carry more current under the same conditions\. It also has to fit the terminals, raceway and box\. Size it for the actual installation\.

How is ampacity measured?

Ampacity is expressed in amperes\. It describes how much current a conductor can carry under the stated conditions without exceeding its temperature rating\.

Can I apply the temperature and conductor\-count factors together?

Yes\. When both factors apply, multiply the table value by the ambient temperature factor and by the current\-carrying conductor count factor\.

## Related calculators

- [Conduit Fill Calculator](/conduit-fill-calculator/)
- [Voltage Drop Calculator](/voltage-drop-calculator/)
- [Wire Size Calculator](/wire-size-calculator/)
- [Box Fill Calculator](/box-fill-calculator/)
- [Three\-Phase Power Calculator](/three-phase-power-calculator/)
- [Circuit Breaker Size Calculator](/circuit-breaker-size-calculator/)

[See where this skill fits on the electrician career path](/career-map/)

## Worked example

If a worksheet starts at a hypothetical 40 A and the verified combined factor is 0\.80, the product is 32 A\. Neither starting value is a code\-table claim\.

1. Record material and the temperature column you are checking\.
2. Multiply the supplied base ampacity by the supplied factors\.
3. Confirm the applicable table and limits separately\.

### how do you read a wire ampacity chart?

Find size and material, select the temperature column, then apply correction and adjustment factors as required\.

### what size wire is in the 50 amp ampacity row?

Check the conductor material, the applicable temperature column and the adopted table\. The 50 A label alone does not identify a conductor size\.

### what size wire is in the 100 amp ampacity row?

In the base table it depends on material and temperature column; dwelling service rules may differ\. Verify both in the 2026 NEC\.

## Sources for the answer and exercise

- [TDLR, Texas adoption of the 2026 NEC](https://www.tdlr.texas.gov/news/rulemaking/2026/09/01/commission-adopts-rules-12/)
- [Southwire building wire selector and stated limits](https://www.southwire.com/calculators/re3%E2%84%A2-building-wire-selector-calculator)

Reference edition\. The preset code values and cited locators on this page are from the 2023 NEC\. Texas adopted the 2026 NEC on September 1, 2026\. For Texas work, verify Table 310\.16 and the associated ambient and conductor\-count adjustment tables in the 2026 edition before applying any result\. [TDLR adoption notice](https://www.tdlr.texas.gov/news/rulemaking/2026/09/01/commission-adopts-rules-12/) \.

## Wire Size and Ampacity: Read the 50 A and 100 A Rows

Look up a starting conductor size by material, terminal temperature column and base ampacity\.

Code basis\. The lookup and the 50 A and 100 A examples use NEC 2023 Table 310\.16 reference rows\. Texas adopted the 2026 NEC effective September 1, 2026; confirm the exact row in 2026 Table 310\.16 and applicable adjustment provisions in 310\.15 before use\. [TDLR adoption notice](https://www.tdlr.texas.gov/news/rulemaking/2026/09/01/commission-adopts-rules-12/) \.

The 2026 edition permits 16 AWG copper or 14 AWG copper\-clad aluminum for qualifying 10 A branch circuits\. Review 2026 NEC 210\.22 and 210\.23 before applying that provision\. [EC\&M 2026 changes](https://www.ecmweb.com/national-electrical-code/code-basics/article/55406560/key-revisions-to-chapter-3-of-the-2026-nec) \.

### Read the base table in reverse

On the 75 °C base rows, 50 A corresponds to 8 AWG copper or 6 AWG aluminum\. The 100 A row corresponds to 3 AWG copper or 1 AWG aluminum\. These are base table lookups\. Termination rules, cable restrictions, load type and overcurrent rules still apply\. Use the adopted NEC edition and the equipment markings before selecting a conductor\.

This is corrected insulation ampacity\. Check the terminal and overcurrent protection limits separately\.

NEC 2023 Table 310\.16 base ampacity in amperes

Size

Cu 60 °C

Cu 75 °C

Cu 90 °C

Al 60 °C

Al 75 °C

Al 90 °C

14 AWG

15

20

25

—

—

—

12 AWG

20

25

30

15

20

25

10 AWG

30

35

40

25

30

35

8 AWG

40

50

55

35

40

45

6 AWG

55

65

75

40

50

55

4 AWG

70

85

95

55

65

75

3 AWG

85

100

115

65

75

85

2 AWG

95

115

130

75

90

100

1 AWG

110

130

145

85

100

115

1/0 AWG

125

150

170

100

120

135

2/0 AWG

145

175

195

115

135

150

3/0 AWG

165

200

225

130

155

175

4/0 AWG

195

230

260

150

180

205

250 kcmil

215

255

290

170

205

230

300 kcmil

240

285

320

195

230

260

350 kcmil

260

310

350

210

250

280

400 kcmil

280

335

380

225

270

305

500 kcmil

320

380

430

260

310

350

## Worked examples

1. 6 AWG copper, 90 °C insulation, 40 °C ambient and six current\-carrying conductors gives 54\.60 A \(75 × 0\.91 × 0\.80\)\.
2. 2 AWG aluminum, 75 °C insulation, 30 °C ambient and three current\-carrying conductors gives 90\.00 A\.

## How the calculation works

Multiply the NEC 2023 Table 310\.16 base ampacity by the ambient factor in Table 310\.15\(B\)\(1\)\(1\) and the conductor\-count factor in Table 310\.15\(C\)\(1\)\. The base table assumes 30 °C ambient and three or fewer current\-carrying conductors\. Verify termination ratings, small\-conductor protection limits, and whether the general adjustment factors apply to the installation\.

## Related calculators

- [Conduit Fill Calculator](/conduit-fill-calculator/)
- [Voltage Drop Calculator](/voltage-drop-calculator/)
- [Wire Size Calculator](/wire-size-calculator/)
- [Box Fill Calculator](/box-fill-calculator/)
- [Three\-Phase Power Calculator](/three-phase-power-calculator/)
- [Circuit Breaker Size Calculator](/circuit-breaker-size-calculator/)

[See where this skill fits on the electrician career path](/career-map/)

### Sources

- [Cerrowire manufacturer ampacity chart](https://www.cerrowire.com/products/resources/tables-calculators/ampacity-charts/) \(checked 2026\-11\-12\)
- [NEC 2023 Table 310\.16 and applicable conditions](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) \(checked 2026\-11\-12\)
- [Southwire sizing references](https://www.southwire.com/calculators) \(checked 2026\-11\-12\)

## Wire Size and Ampacity

Wire size is chosen by comparing the load current to the conductor’s allowable ampacity, then checking voltage drop, insulation temperature rating, bundling and terminations\. Larger conductors have lower resistance and carry more current\. Final sizing for real circuits follows the adopted code and a qualified designer, not a quick calculator result\.

### Apply it to a practice example

Hypothetical worked math for voltage drop concepts: a 15 A load over a conductor with 0\.4 Ω round\-trip resistance drops 15 × 0\.4 = 6 V\. On 120 V that is 5%\. The example shows why length matters\. Look up ampacity in the current code with a qualified person\.

### Sources

- [Primary reference](https://www.nfpa.org/en/Codes-and-Standards/Document-information-pages/70) \(checked November 12, 2026\)
- [Texas NEC adoption notice](https://www.tdlr.texas.gov/news/rulemaking/2026/09/01/commission-adopts-rules-12/) \(checked November 12, 2026\)
