# NEC Article 430: Motor Circuit Sizing and Protection

NEC Article 430 uses different rules for motor conductors, overload protection, and branch\-circuit short\-circuit and ground\-fault protection\. Start by identifying the motor type and supply\. Then determine which current value applies to each calculation, because the same number is not used for every device\.

Working Article 430 problems for the Texas exam? As an Amazon Associate, Tsai Electro earns from qualifying purchases\. Our own [Texas Journeyman Electrician Exam Prep 2026 NEC paperback](https://www.amazon.com/dp/B0HMLXV8G7?tag=tsaielectro0c-20) \(also on [Kindle](https://www.amazon.com/dp/B0HMP9YZ4F?tag=tsaielectro0c-20) \) has worked calculations and code book lookup paths\. For the job site, [Ugly’s Electrical References, 2026 Edition](https://www.amazon.com/dp/1284315754?tag=tsaielectro0c-20) keeps motor formulas and tables in your tool bag\.

## Worked example: a 5 hp, 460 V three\-phase motor

Assume a continuous\-duty motor with a nameplate current of 7\.0 A\. Use each current for the step that calls for it\.

Step

Calculation or lookup

1\. Table 430\.250 full\-load current

5 hp at 460 V gives 7\.6 A table FLC\.

2\. Conductor ampacity

7\.6 A × 125% = 9\.5 A minimum before applicable adjustments or other installation requirements\.

3\. Branch\-circuit short\-circuit and ground\-fault protection

Start with 7\.6 A table FLC\. Select the protective device type and apply its specific value from 430\.52\.

4\. Separate overload protection

Use the 7\.0 A nameplate current\. The 115% limit is 8\.05 A\. When the motor qualifies for the 125% limit by its marked service factor or temperature rise, that limit is 8\.75 A\.

Source: [NFPA Table 430\.250 record](https://docinfofiles.nfpa.org/files/AboutTheCodes/70/70_A2025_NEC_P11_FD_FRStatements.pdf) \.

Source: [NFPA record for motor overload protection](https://docinfofiles.nfpa.org/files/AboutTheCodes/70/70_A2019_NEC_P11_FD_PISubmittals.pdf) \.

Source: [NFPA 70 and edition selector](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) \.

[Continue with the electrical practice guides](/membership/)

As an Amazon Associate we earn from qualifying purchases\.

Short answer: For standard motor circuit problems, take full\-load current from the NEC motor tables, not the nameplate, to size conductors and short\-circuit protection\. Conductors are sized at 125% of that current\. Overloads use the nameplate current, usually at 115% or 125% depending on the motor\. In the standard cases in this article, an inverse\-time breaker may be up to 250% of table current, and the next standard size up is allowed when the result does not land on one\. Read the Article 430 exceptions for other cases\.

Motor questions mix three different percentages, and one wrong pick costs the point\. The PSI outline gives Motors and [Generators](https://www.tsaielectro.com/nec-445-generators-apprentice/) 5 items in Texas Journeyman NEC Knowledge and 2 in Calculations\. The Texas Journeyman Practice Pack has step\-by\-step solutions for 299 calculation questions, each showing which table and which percentage applies\. US$39 once\.

Check your motor steps

Tsai Electro is an independent learning site\. Not affiliated with TDLR, PSI or NFPA\. We explain the method in our own words and do not reproduce NEC text\. Check every rule and table value in your own 2026 NEC\. Motor circuits on the job are sized by the people responsible for the design; this page is for learning the method\.

## Article 430 map

Article 430 is long because a motor circuit has several separate parts, and each part has its own rule\. Texas uses the 2026 NEC for installations and exams from September 1, 2026 \( [TDLR rule adoption notice](https://www.tdlr.texas.gov/news/rulemaking/2026/09/01/commission-adopts-rules-12/) , [PSI Candidate Information Bulletin](https://test-takers.psiexams.com/api/content/bulletin/1682) \)\.

Part of the circuit

What it protects or does

Current you use

Where to look

Branch\-circuit conductors

Carry the motor current

125% of table full\-load current

430\.22

Overload protection

Protects the motor from running too hot

Nameplate full\-load amps

430\.32

Short\-circuit and ground\-fault protection

Breaker or fuses for faults

Table full\-load current × the percentage in the table

Table 430\.52\(C\)\(1\)

Feeder conductors \(several motors\)

Carry more than one motor

125% of the largest plus the rest

430\.24

Feeder protection

Feeder breaker or fuses

Largest branch device plus the other motors

430\.62\(A\)

Control circuit

Start, stop and interlock wiring

Control\-circuit rules

430\.72

Disconnecting means

Lets you shut off motor and controller

In sight of both, with exceptions

430\.102

The first rule to learn: for conductors and short\-circuit protection, use the full\-load current from the NEC tables \(430\.6\(A\)\)\. Use the nameplate current only for overloads\. Single\-phase motor currents are in Table 430\.248 and three\-phase in Table 430\.250\.

## Values used in the examples

Check each one in your own 2026 NEC\.

Item

Value

10 hp, 460 V, three\-phase, table full\-load current

14 A

15 hp, 460 V, three\-phase, table full\-load current

21 A

3 hp, 230 V, single\-phase, table full\-load current

17 A

Overloads, service factor 1\.15 or more

125% of nameplate

Overloads, all other motors \(simplified\)

115% of nameplate

Inverse\-time breaker

250% of table current

Dual\-element \(time\-delay\) fuse

175% of table current

When the percentage gives a size that is not a standard rating, you may go up to the next standard size \(430\.52\(C\)\(1\)\)\.

## Worked example 1: one 10 hp motor

A 10 hp, 460 V, three\-phase motor\. Nameplate full\-load amps 13\.2 A, service factor 1\.15\. Terminals are rated 75°C\.

1. Table full\-load current: 14 A\. \(Not the 13\.2 A on the nameplate\.\)
2. Conductor ampacity: 14 × 1\.25 = 17\.5 A minimum\. At the 75°C column, 14 AWG copper \(20 A\) meets this\. Article 430 sets motor\-circuit protection, so the general 15 A limit for 14 AWG does not apply \(240\.4\(G\)\)\. Many shops still run 12 AWG as a company standard\.
3. Overload: nameplate 13\.2 × 1\.25 = 16\.5 A maximum setting\.
4. Inverse\-time breaker: 14 × 2\.50 = 35 A\. 35 A is a standard size, so 35 A\.
5. Dual\-element fuse instead: 14 × 1\.75 = 24\.5 A\. Next standard size up: 25 A\.

Check: reverse each step\. 17\.5 ÷ 1\.25 = 14\. 16\.5 ÷ 1\.25 = 13\.2\. 35 ÷ 2\.5 = 14\. 24\.5 ÷ 1\.75 = 14\. All match\.

## Worked example 2: one 15 hp motor

A 15 hp, 460 V, three\-phase motor\.

1. Table full\-load current: 21 A\.
2. Conductor ampacity: 21 × 1\.25 = 26\.25 A minimum\.
3. Inverse\-time breaker: 21 × 2\.50 = 52\.5 A\. Not a standard size\. Next standard size up: 60 A\.
4. Dual\-element fuse: 21 × 1\.75 = 36\.75 A\. Next standard size up: 40 A\.

Check: 50 A is the standard size just below 52\.5, and 52\.5 is more than 50, so the rounded\-up answer must be 60\. 35 A is below 36\.75, so the fuse answer must be 40\.

## Worked example 3: a feeder for both motors

The 10 hp and 15 hp motors share one feeder\.

1. Feeder conductor ampacity: 125% of the largest motor plus 100% of the other: \(21 × 1\.25\) \+ 14 = 26\.25 \+ 14 = 40\.25 A minimum\.
2. Feeder breaker: not more than the largest branch\-circuit device plus the full\-load current of the other motor: 60 \+ 14 = 74 A\.
3. 74 A is not a standard size, and this rule does not let you round up\. Use the next standard size down: 70 A\.

Check: add in another order\. 14 \+ 26\.25 = 40\.25\. And 70 is the largest standard size that is not more than 74\.

## The three\-wire start\-stop circuit

The most common control circuit you will wire is the three\-wire start\-stop station\.

- The stop button is normally closed and is wired in series, so pressing it breaks the circuit\.
- The start button is normally open\. A holding \(seal\-in\) contact on the starter is wired in parallel with it, so the coil stays energized after you let go\.
- The overload contacts are in series with the coil, so an overload trip drops the starter out\.
- If power fails, the coil drops out and the motor stays off until someone presses start again\. A two\-wire control, like a float switch, restarts on its own when power returns\.

Before tracing a starter circuit, follow the lockout/tagout procedure of your employer, and have a qualified person verify the absence of voltage with a test instrument\. Do not assume a circuit is safe because a switch is off\. See the [NFPA 70E and lockout article](/nfpa-70e-lockout-tagout-apprentice/) before you work on any starter\.

## Identify the task before choosing a motor value

Keep three ideas separate in your notes: the motor that converts electrical energy to motion, the control that commands operation, and the protection or conductors being selected\. A value suitable for one calculation is not automatically the required input for every other task\.

Add a transformer concept check as a separate problem\. In the ideal, lossless classroom model, a transformer with a 4:1 primary\-to\-secondary turns ratio has a secondary voltage one quarter of the primary voltage\. At 480 V primary, that is 120 V secondary\. If the secondary supplies 8 A in this model, its 960 VA corresponds to 2 A on the primary\. This is theory practice, not conductor or protective\-device sizing\.

For any actual motor or transformer code question, name the exact task first, then record the applicable 2026 NEC reference, required current basis, supplied ratings, and calculation\. Do not borrow a motor rule for a transformer question merely because both involve current\.

### Motor and ideal\-transformer practice

1. TX\-117: Does a start command by itself establish that equipment is safe to touch? Answer: No\. A control command is not an electrical\-safety isolation procedure; this exercise involves no physical work\.
2. TX\-117: For the ideal 4:1 transformer, what is the secondary voltage with 480 V primary? Answer: 120 V: divide 480 by 4\.
3. TX\-117: Does an ideal\-transformer calculation determine the permitted protective device for an installation? Answer: No\. That is a separate code and equipment question\.
4. TX\-163: At 120 V and 8 A, what is the secondary apparent power in the ideal example? Answer: 960 VA\.
5. TX\-163: For 960 VA at 480 V primary in the same ideal example, what is primary current? Answer: 2 A\.
6. TX\-163: A separate classroom problem supplies 20 A and explicitly directs multiplication by 125%\. What is the arithmetic result? Answer: 25 A\. This supplied multiplier is problem data, not a universal rule for every motor task\.

### Official references checked October 16, 2026

- [U\.S\. Department of Energy: Electrical Science, Volume 4](https://www.energy.gov/ehss/articles/doe-hdbk-10114-92)
- [NFPA 70 official standard page](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)

## Motor circuit practice: which current value belongs in each step?

Quick answer: before you multiply by 125%, identify which task you are solving\. For a standard motor branch\-circuit example, the conductor and short\-circuit protective device start from the applicable NEC motor table full\-load current\. The overload device starts from motor nameplate current\.

1\. Choosing branch\-circuit conductor ampacity

Motor table full\-load current

Nameplate current

Voltage alone

See the rule

Start from the relevant motor full\-load current table for the motor type, voltage and horsepower\. For the usual continuous\-duty single\-motor example, compare at least 125% of that table current to permitted conductor ampacity\.

2\. Choosing the current for overload protection

Motor table full\-load current

Motor nameplate full\-load current

Voltage alone

See the rule

The overload setting is based on motor nameplate current, with the applicable percentage and motor characteristics checked separately\.

3\. Starting a branch\-circuit short\-circuit device calculation

Motor table full\-load current

Nameplate current alone

Line voltage alone

See the rule

Use the applicable motor table current and the protective\-device rule for this task\. This is different from overload protection\.

Choose one option in each card, then check your selections\.

More practice: [free Texas Journeyman questions](https://www.tsaielectro.com/texas-journeyman-electrician-practice-test/) \. Source reading: [Rockwell’s motor circuit design introduction](https://literature.rockwellautomation.com/idc/groups/literature/documents/at/ic-at001_-en-p.pdf) \. The full installation design also depends on the applicable 2026 NEC sections, device characteristics and site conditions\.

## Check yourself

Our own practice questions\. Answers below each\.

1. 3 hp, 230 V, single\-phase motor\. Minimum conductor ampacity? Answer: 17 × 1\.25 = 21\.25 A\.
2. Same motor, inverse\-time breaker? Answer: 17 × 2\.5 = 42\.5 A, not standard\. Next size up: 45 A\.
3. A motor nameplate reads 20 A, service factor 1\.0, no temperature\-rise marking\. Maximum overload setting under the simplified rule? Answer: 20 × 1\.15 = 23 A\.
4. Which current do you use for the overload: table or nameplate? Answer: Nameplate\.

Disclosure: If you buy through the Amazon link below, Tsai Electro may earn a commission at no extra cost to you\. As an Amazon Associate I earn from qualifying purchases\.

### Formulas and control diagrams in your pocket

Ugly’s Electrical References, 2026 Edition\. The publisher’s description lists formulas, NEMA configurations, conduit bending and fill, ampacity, and transformer and control circuit wiring diagrams\. It is a field reference, not a substitute for the NEC, and spiral\-bound books are not allowed in the Texas exam room\.

Check price on Amazon

## FAQ

### Do you use nameplate or table current for motor wire size?

Table current\. For branch\-circuit conductors and short\-circuit protection, the NEC requires the full\-load current from its motor tables\. Nameplate current is used for sizing overload protection\.

### How do you size a breaker for a motor?

Multiply the table full\-load current by the percentage for the device type in the NEC motor protection table\. For an inverse\-time breaker that is 250%\. If the result is not a standard size, you may use the next standard size up\.

### Why is motor wire sized at 125%?

The NEC requires branch\-circuit conductors for a single continuous\-duty motor to have an ampacity of at least 125% of the motor’s table full\-load current, which gives margin for running at full load\.

### What is the difference between overload and short\-circuit protection for a motor?

Overload protection trips on sustained current above the motor rating and protects the motor from overheating\. Short\-circuit and ground\-fault protection, the breaker or fuses, opens quickly on faults and is sized much larger so the motor can start\.

### What is the 125% rule?

For a single continuous\-duty motor, 430\.22 generally bases conductor ampacity on 125% of table FLC\. The separate overload calculation in 430\.32 starts from nameplate current and has its own conditions\.

### How to calculate FLA on a 3\-phase motor?

For the overload calculation, read the rated current directly from the motor nameplate at the connection voltage\. Use the applicable NEC table current for the steps that call for FLC\.

Next step: practice motor problems on exam time\. The Texas Journeyman Practice Pack has 10 timed two\-part mocks on the 2026 NEC\. After each one you see your score for each official topic area, including motors and generators, so you can see where to practice next\. US$39 once\.

Take a timed mock

Next skill: industrial controls\. Motor starters lead to PLCs and drives: [the industrial electrician career roadmap](/industrial-electrician-career-roadmap/) \.

## Sources checked October 2026

- TDLR rule adoption notice, 2026 NEC: [https://www\.tdlr\.texas\.gov/news/rulemaking/2026/09/01/commission\-adopts\-rules\-12/](https://www.tdlr.texas.gov/news/rulemaking/2026/09/01/commission-adopts-rules-12/)
- PSI Candidate Information Bulletin for TDLR \(updated 9/15/2026\): [https://test\-takers\.psiexams\.com/api/content/bulletin/1682](https://test-takers.psiexams.com/api/content/bulletin/1682)
- TDLR exam page \(spiral\-bound books not allowed\): [https://www\.tdlr\.texas\.gov/electricians/elecexam\.htm](https://www.tdlr.texas.gov/electricians/elecexam.htm)
- NFPA 70 \(NEC\), 2026 edition, Article 430 and its motor tables, read in your own copy: [https://www\.nfpa\.org/codes\-and\-standards/nfpa\-70\-standard\-development/70](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)