# Weekly electrician practice: box\-fill worked example

TSAI ELECTRO \| WEEKLY PRACTICE 01

## How much box volume is enough?

Six insulated 12 AWG conductors enter a box and are spliced or terminated\. It contains one single\-gang device yoke connected to 12 AWG conductors, internal clamps and four entering 12 AWG equipment grounding conductors\. There are no support fittings, terminal\-block assemblies or long loops\. What minimum volume do these fill allowances require?

A 18\.00 in³ B 20\.25 in³ C 22\.50 in³ D 27\.00 in³

Check your answer and the counting steps

C: 22\.50 cubic inches\.

1. Six insulated conductors: 6 allowances\.
2. One single\-gang yoke: 2 allowances, using its largest connected conductor\.
3. All internal clamps together: 1 allowance\.
4. Four entering equipment grounds: 1 allowance, using the largest entering ground\.

\(6 \+ 2 \+ 1 \+ 1\) × 2\.25 = 22\.50 in³ \.

NEC 2026: 314\.16\(B\)\(1\), \(B\)\(2\), \(B\)\(4\), \(B\)\(5\) and Table 314\.16\(B\)\(4\)\. The question intentionally uses one conductor size; different sizes and other fittings need their own checks\.

Original study question; no official exam item is reproduced\. Check the complete rule and local requirements\. [Official NFPA reader](https://link.nfpa.org/free-access/publications/70/2026) \.

[More free practice by Tsai Electro](https://www.tsaielectro.com/practice/exam/us/en/)