Single / Three-Phase Power Calculator (kW • kVA • kVAR • Amps)

In practice, this three phase power calculator gives you the fast numbers you need before you size a breaker or pull wire. Additionally, it also works as a single phase power calculator: enter voltage, current and power factor (PF), then solve for kW, kVA, kVAR or amps. Therefore, it’s tuned for 120/240 V and 208/240/277/480 V jobs.

Single / Three-Phase Power Calculator

Convert between P (kW), Q (kvar), S (kVA), current (A) with single- or three-phase systems.

three phase power calculator

Three phase power calculator — quick start

Why it matters

in real jobs, mixing up kW vs kVA or forgetting PF leads to change orders, nuisance trips, and callbacks. Therefore, doing the power-triangle math up front saves both time and money.

How to use three phase power calculator

  1. System — pick Single-phase or Three-phase.
  2. Solve for — choose what you need: kW, kVA, kVAR or Amps.
  3. Enter inputs — voltage (use line-to-line for three-phase), the known current or power, and PF (0–1).
  4. Calculate — you’ll get an answer plus the other triangle values. If something looks off, adjust PF or verify whether you used VL-L vs VL-N.

Tip: For motors, PF varies with loading. As a result, nameplate PF or measured PF gives better amp estimates than guessing 1.0.

Power-triangle refresher (kW, kVA, kVAR)

  • kW (P) — real power that does the work (heat, torque, light).
  • kVA (S) — apparent power seen by the source.
  • kVAR (Q) — reactive power from magnetizing/charging currents.
  • PF = kW / kVA. Therefore, for a given kW, a lower PF means higher amps.

Core formulas (balanced systems):

  • Single-phase:
    • kW = V × I × PF
    • kVA = V × I
  • Three-phase (use line-to-line voltage VL-L):
    • kW = √3 × VL-L × I × PF
    • kVA = √3 × VL-L × I
  • Reactive: kVAR = √(kVA² − kW²) = kW × tan(arccos PF)

Field examples you can sanity-check

  • Amps from kW (3ϕ 480 V): 10 kW at PF 0.90 → I ≈ 10,000 / (√3 × 480 × 0.90) ≈ 13.4 A.
  • kW from amps (1ϕ 240 V): I = 40 A, PF 0.95 → kW = 240 × 40 × 0.95 = 9.12 kW.
  • kVAR from kW & PF: 20 kW at PF 0.80 → kVAR = 20 × tan(arccos 0.80) ≈ 15 kVAR.
  • Heads-up: If your three-phase voltage is 208 V (wye), remember it’s line-to-line. Otherwise, using 120 V will under-estimate amps by roughly √3.

When to use three phase power calculator vs other tools

  • Sizing feeders and services — start here to get kW/kVA and Amps, then jump to your Wire Size or Voltage Drop tool.
  • Motor / EVSE planning — use actual PF if you have it; in addition, consider inrush and duty cycle when selecting OCPD and conductors.
  • Generator / UPS estimates — convert kW ↔ kVA quickly and pick a sensible PF; meanwhile, leave margin for starting loads.
  • Panel balancing — calculate each large load; consequently, you’ll keep phases even and the neutral cool.

Common mistakes (and how to avoid them)

  • Using VL-N on three-phase — the math expects VL-L. Double-check your meter readout.
  • Assuming PF = 1 — lighting with modern drivers may be close, but motors and welders rarely are.
  • Confusing hp with kW — don’t forget motor efficiency and PF; hp × 0.746 gives shaft kW only.
  • Unbalanced loads — this calculator assumes balanced three-phase; if not, solve phase by phase.

Practical workflow (fast and repeatable)

  1. Estimate PF from nameplate or past jobs.
  2. Solve for amps, then check breaker and conductor against ampacity and temperature corrections.
  3. Therefore, if voltage drop is near your target, upsize the conductor now rather than fixing callbacks later.
  4. Finally, document assumptions (PF, efficiency, duty) in your notes or quote.

Extended reading & internal resources about three phase power calculator

  • Voltage Drop Calculator
  • Wire Size & Ampacity/wire-size-ampacity
  • Panel upgrades & breaker selection/panel-upgrade
  • AFCI/GFCI protection basics/afci-gfci-guide

References (open in a new tab)

Disclaimer: This power calculator is for education and pre-design checks. Final selections must follow the NEC and local amendments, equipment listings, and your AHJ or project engineer.

FAQ

Q1. Should I use line-to-line or line-to-neutral voltage for three-phase?

Use line-to-line (VL-L) for these formulas. Otherwise, your amps will be under-estimated by about √3.

Q2. What PF should I assume if I don’t have data?

Lighting with modern drivers may be ~0.95–0.99; small motors might be 0.75–0.90; welders and VFDs vary. Therefore, confirm whenever possible.

Q3. Does this include efficiency?

No—efficiency is separate from PF. For motors, convert horsepower to shaft kW (hp × 0.746), then divide by efficiency to get input kW before applying PF.

Q4. Can I switch between 1-phase and 3-phase on the fly?

Yes. Meanwhile, use 120/240 V for residential and 208/240/277/480 V for commercial; the math updates instantly.

Scroll to Top