Skip to main content
Not selected · English · Dual units
My account Join free Start free test
Home Voltage Drop Calculator for Single-Phase and 3-Phase Circuits

Voltage Drop Calculator for Single-Phase and 3-Phase Circuits

Use this single-phase and 3-phase voltage drop calculator to estimate voltage lost along a circuit from its load current, one-way length and conductor resistance.

As an Amazon Associate we earn from qualifying purchases.

Single-phase and 3-phase voltage drop formulas

With conductor area CM in circular mils and one-way length L in feet, estimated drop is 2 × K × I × L ÷ CM for single-phase, or 1.732 × K × I × L ÷ CM for balanced three-phase. IAEI uses K = 12.9 for copper and 21.2 for aluminum.

Worked example: 6 AWG copper, 44 A, 160 ft one way, and 240 V single-phase gives approximately 6.9 V of drop, or 2.9%.

Source: IAEI Voltage Drop Formulas.

Measuring voltage drop on site

Voltage drop is the difference between source and load voltage under the assumed load. For a simple resistive circuit, use current times the total path resistance. A balanced three-phase calculation uses a different line-to-line relationship. State the circuit type, units and assumptions before comparing the estimate with a design target.

The branch result is an estimate. Add the feeder percentage on the same nominal-voltage basis to see the combined estimate.

Preset values are from the 2023 NEC. Check the current adopted edition before use.

Worked examples

  1. 120 V single phase, 16 A, 100 ft one way, 12 AWG copper and 1% feeder drop gives 6.34 V (5.28%) on the branch and 6.28% total.
  2. 480 V three phase, 40 A, 200 ft one way and 8 AWG copper gives 10.78 V (2.25%). A feeder value is needed for the total check.

How the calculation works

Multiply current, one-way length in thousands of feet, and resistance per 1,000 feet. Multiply by 2 for a two-wire single-phase circuit or √3 for balanced three phase. The model uses NEC Chapter 9, Table 8 DC resistance for stranded, uncoated copper at 75 °C. Only sizes with verified resistance are shown. The model does not include reactance, power factor, or parallel runs. The 3% branch and 5% combined values are NEC informational recommendations for the general case.

Frequently asked questions

How to calculate voltage drop in a wire?

Enter the one-way length, current and conductor. For a two-wire single-phase circuit, the tool multiplies current by the resistance of the out-and-back path. It uses a different multiplier for balanced three phase.

How far can you run 12 AWG wire before A voltage drop?

Voltage drop begins as soon as current flows through a conductor with resistance. The usable length depends on the material, current, voltage and your target percentage.

What is the voltage drop for 14 AWG wire?

There is no single drop for a wire size. The result depends on current, length, material and circuit type. Check whether the size is available in the tool’s verified data before using it.

3 phase voltage drop formula

For the balanced three-phase resistance estimate, multiply the square root of three by line current, one-way length in thousands of feet and resistance per thousand feet.

Related calculators

See where this skill fits on the electrician career path

Worked example

For a 20 A study load and 0.40 Ω of total loop resistance, the estimated drop is 8 V. Relative to a 120 V source that is about 6.7%. The resistance is supplied for the exercise.

  1. Write down the current and the full path resistance.
  2. Multiply and divide the result by source voltage for a percentage.
  3. For AC with significant reactance, use a model that includes it.

how do you calculate voltage drop in a single phase circuit?

For a simple resistive single-phase model, multiply current by total loop resistance. Include both outgoing and return paths.

how do you calculate voltage drop in a three phase circuit?

Use the balanced three-phase model and compare line-to-line values. Check the calculator’s impedance and power-factor assumptions.

what do the 3 and 5 percent voltage drop guidelines mean?

They are design recommendations, often 3 percent for a branch circuit and 5 percent total, not universal mandates. Check the edition and your project specification.

Which voltage should I enter for balanced three-phase?

Enter the line-to-line supply voltage.

Should I enter one-way or round-trip length?

Enter one-way length. The multiplier accounts for the circuit configuration.

Does the result establish conductor ampacity?

Use the result as a voltage-drop estimate. Verify conductor ampacity and termination ratings separately.

Sources for the answer and exercise

Reference edition. The preset code values and cited locators on this page are from the 2023 NEC. Texas adopted the 2026 NEC on September 1, 2026. For Texas work, verify Chapter 9 Table 8 and the voltage-drop informational notes in the 2026 edition before applying any result. TDLR adoption notice.

Voltage Drop: Copper and Aluminum Worked Check

Use an independently verified conductor resistance and show both the branch result and the combined feeder-plus-branch result. For balanced three-phase, enter line-to-line voltage.

Code basis. The 3% branch and 5% combined guidance and the example conductor resistance use NEC 2023 reference values. Texas adopted the 2026 NEC effective September 1, 2026; for current design, verify the voltage-drop notes in 2026 NEC 210.19 and 215.2 and the applicable Chapter 9 Table 8 or 9 conductor data. TDLR adoption notice.

Enter your values.

This resistance-only check accepts either material using the resistance you enter. Use the conductor manufacturer’s value at the relevant temperature. For circuits where reactance and power factor materially affect the result, use the existing calculator below with supported inputs or an engineering calculation.

Check the two voltage-drop budgets

  1. Use one-way length. The multiplier accounts for the circuit configuration.
  2. In a practice case with 120 V, 16 A, 100 ft and 1.98 Ω/1000 ft, 2 × 16 × 100 × 1.98 ÷ 1000 = 6.336 V.
  3. 6.336 ÷ 120 = 5.28%. Adding the sample 1% feeder gives 6.28%, above the commonly used 3% branch and 5% combined design guidance. Other applications may have specific requirements.

Sources

★ Resources
Scroll to Top
Not a licensed Professional Engineer in Texas or any U.S. state. Does not offer engineering services. Exam-prep education only.