AC impedance and the power triangle

Learning evidence

  1. Viewed
  2. Practiced
  3. Assessment passed
  4. Practical task completed

Join to track your progress

Light it up

view, practice, pass the check, do the task
PackTexas Journeyman Exam Practice Pack
Member toolProgress log — records each of the 4 evidence steps
Next stationCT ratio, displayed units and uncertainty →

Electrician helper / apprentice-entry → Journeyman Electrician · 15 skill stations

Relate AC impedance to the quantities shown in a power triangle.

What you’ll do

  • Your attempt
  • Try a changed case
  • Evidence to prepare
First step

For an AC series circuit, treat R and X as the legs of an impedance triangle, and divide RMS voltage by the impedance magnitude to get RMS current. Watts follow R, var follow X, and VA is the hypotenuse of the power triangle. Common misconception: watts, var and VA can simply be added together, and the sign of var is arbitrary. Correct practice: combine W and var at a right angle to find VA, and give inductive and capacitive reactance opposite signs. Sketch both triangles before calculating, labeling each side with its unit and sign. If a changed paper case swaps an inductor for a capacitor, flip the sign of X and redraw both triangles.

You’re at Level 1. Next: Read a control-state model and find an invalid inference. Membership guides you through it.

You’re at Level 1. Next: Read a control-state model and find an invalid inference. Membership guides you through it.

See membership

Practice for this step: 3 questions

Choose one answer per question. This practice runs in your browser.

A plant load of 50 kilowatts runs at a power factor of 0.80 lagging. Capacitors will raise the power factor to 0.95. The tangent of the power-factor angle is 0.750 at 0.80 and 0.3287 at 0.95. How many kVAR of capacitors are needed, to the nearest 0.1 kVAR?
A 0.05-henry coil is connected to a 60-hertz supply. What is its inductive reactance, to the nearest 0.1 ohm?
A 100-kW, 480Y/277-volt, three-phase generator is rated at a power factor of 0.8. The conductors from its output terminals to the first overcurrent device must have an ampacity of at least 115% of the nameplate current. The THHN copper conductors run where the ambient correction factor for the 90 degree C column is 0.82 (given), with three current-carrying conductors in the raceway, and all terminals are rated 75 degrees C. Copper ampacities (75 C / 90 C): 1/0 AWG 150 / 170 A; 2/0 AWG 175 / 195 A; 3/0 AWG 200 / 225 A; 4/0 AWG 230 / 260 A. What is the smallest conductor permitted?