Not selected · English · Dual units
My account Join free Start free test
Home Voltage Drop Calculator (Single & Three-Phase)

Voltage Drop Calculator (Single & Three-Phase)

For study estimates only, not engineering design

This voltage drop calculator helps you size conductors and check percent voltage drop before you pull wire. Enter the supply voltage, load current, one-way run length, and conductor material (copper or aluminum) and get the drop in volts (V) and percent drop (%). You’ll also see a quick wire size suggestion as a starting point.
Common field practice in the U.S. follows the “3% per branch, 5% total” guideline (NEC informational note). Always verify with the code and local requirements.

Contents

Result

Voltage drop V
Drop %
Voltage at the load V
Check
Suggested wire size

Numbers check out? The next step is the licensing exam: take a practice test for the country you picked.

This is an estimating tool. Follow your local electrical code and have a qualified electrician confirm any real installation.

On the Texas Journeyman exam

Where this calculation shows up

On the PSI Texas Journeyman exam this is part of the Calculations part: Branch Circuit Calculations and Conductors. That part has 26 questions in 110 minutes, and you need 70% on it on its own.

Try an exam-style calculation (our own numbers): A 120 V single-phase load draws 16 A at the end of a 100 ft run (one way). Each conductor has 0.2 ohm of resistance per 100 ft (given). What is the voltage drop?

  1. A. 1.6 V
  2. B. 3.2 V
  3. C. 6.4 V
  4. D. 12.8 V
Show the answer

C. 6.4 V. Current flows out and back, so the wire length is 2 x 100 ft = 200 ft, or 0.4 ohm. VD = I x R = 16 x 0.4 = 6.4 V, which is 5.3% of 120 V. Counting one way only gives 3.2 V.

Exam format from the PSI candidate bulletin, read October 3, 2026.

Voltage Drop Calculator

What is voltage drop and why it matters

Voltage drop happens because every conductor has resistance; as a result, the longer the run and the higher the current, the more voltage you lose before the load. Consequently, lights may dim, motors may struggle to start, and EV chargers may ramp down. In practice, keeping the drop within targets protects equipment and improves performance. Therefore, most U.S. designers follow the “3% per branch, 5% total” guideline from NEC’s informational note. Even so, always confirm with your adopted code and local amendments.

How to use Voltage Drop Calculator

First, choose Single-phase or Three-phase. Next, set the supply voltage—120/240 V for residential or 208/240/277/480 V for commercial jobs. Then, enter the expected load current (A). After that, type the one-way length from source to load; the tool handles loop length internally. Meanwhile, select Copper (Cu) or Aluminum (Al). Additionally, pick an allowed percent drop—3% is a common branch target, while 5% covers feeder plus branch. Finally, click Calculate to get Voltage drop (V) and Percent drop (%). If the result exceeds your limit, try a larger AWG, shorten the run, raise system voltage where allowed, or split the load. For example, a 120-V, 15-A lighting run at 140 ft often needs #12 Cu even if #14 passes ampacity.

When to upsize wire or adjust the design

  • Near the limit – if the result shows 2.8–3.2%, bump the conductor up one AWG or consider three-phase where available.
  • Motor/EV/heavy start – keep branch drop under 3% (or even lower) to protect starting torque and reduce flicker.
  • Long exterior runs – driveway lighting, detached garages, docks: upsizing wire often beats fighting callbacks.
  • Feeder + branch combo – check both stages; a “good” branch can still fail if the feeder already used up the margin.

Design & safety notes with Voltage Drop Calculator

Passing a voltage-drop check doesn’t guarantee ampacity or temperature rise compliance. Always verify: installation method, ambient temperature, grouping/derating, termination ratings, and OCPD coordination. Aluminum terminations require listed lugs and correct torque. Three-phase uses a different coefficient than single-phase; this calculator applies standard engineering approximations for a fast check.

Examples you’ll see in the field about Voltage Drop Calculator

  • 120 V, 15 A lighting run, 140 ft – #14 may pass ampacity but miss 3% drop; #12 often fixes it.
  • 240 V, 40 A EV charger, 90 ft – borderline on #8 Cu? Upsize to #6 Cu or shorten the route.
  • 277/480 V fan at 300 ft – three-phase geometry helps, but you’ll still likely bump a size for 3% targets.

Extended reading & internal resources

References about Voltage Drop Calculator

  • Voltage drop
  • Engineering Toolbox — Copper/Aluminum resistivity tables
  • NEC “3%/5%” design guidance (informational note; check your adopted code)

Disclaimer: This Voltage Drop Calculator is for education and pre-design checks. Final conductor sizing must follow the NEC and local amendments, equipment listings, and the project engineer/authority having jurisdiction.about Voltage Drop Calculator

Studying for the Texas Journeyman exam? Calculations are one of its two timed parts. See what the Calculations part tests and how to solve each type, or try 70 free questions. All Texas electrician exams.

FAQ

Q1. What does “3% branch, 5% total” really mean?

A. It’s a common design guideline: try to keep voltage drop on any single branch circuit within about 3%, and keep the total drop from service to the farthest outlet (feeder + branch) within about 5%. It’s an informational note, not a hard code rule—always follow your adopted electrical code and local amendments.

Q2. Should I enter one-way distance or round-trip distance?

A. This calculator expects one-way run length from source to load. It automatically accounts for the round-trip path of the current when computing loop resistance, so you don’t need to double the distance manually.

Q3. Which voltage do I enter for three-phase circuits?

A. For single-phase, just enter the nominal line voltage (120 V, 240 V, 230 V, etc.).
For three-phase, choose the correct option in the “3φ load type” field:
Line-to-line (L-L) for 208/240/480 V loads
Line-to-neutral (L-N) for 120/230 V three-phase four-wire systems
The tool adjusts the geometry factor internally based on this choice.

Q4. How do I choose a good “allowed % drop” value?

A. For most lighting and receptacle circuits, designers often target around 2–3% on the branch circuit. Long feeders or sensitive equipment may need even tighter limits. Some heavy-duty loads (motors, EV chargers, welding machines) may tolerate a bit more drop, but check the manufacturer’s recommendations and your local code first.

Q5. Can I select wire size directly from this result and skip ampacity tables?

A. No. The suggested size is based mainly on voltage drop, with a friendly ampacity warning. Final conductor selection must still respect ampacity, insulation rating, temperature, installation method, correction factors, and any local rules. Treat this calculator as a pre-design check, not a replacement for official tables.

Q6. How accurate is the “include reactance & PF” option?

A. With the option turned off, the tool uses a resistive approximation that’s usually fine for short runs and typical branch circuits. Turning it on adds a simplified reactance model plus power factor, which is more representative for long runs and motor loads. It’s still an engineering estimate—always verify with detailed design when you’re close to limits.

Q7. Can I use this calculator for aluminum conductors or underground cable?

A. Yes, you can choose Copper (Cu) or Aluminum (Al) in the material field; the resistivity values are adjusted accordingly. However, underground runs and special cable types may have different thermal conditions and installation rules, so always cross-check with the cable manufacturer’s data and local code.

Q8. Does this tool support both AWG and mm²? How should I read the result?

A. You can either let the tool auto-suggest a size or enter a specific mm² or AWG value. Results are shown in a dual format like “12 AWG (≈ 3.3 mm²)” so you can match either U.S. or metric conventions. When in doubt, choose the next larger standard size and verify ampacity from your preferred table.

Turn a voltage-drop check into exam practice

Before using a calculator, write down the circuit type, voltage, load current, one-way distance and the conductor data supplied by the question. Keep those inputs with your handwritten calculation so a different result can be traced to a specific input or operation.

Our Texas Journeyman workbook includes worked voltage-drop practice alongside other calculation topics. To see how the explanations handle the givens, units and wrong choices, try a complete worked example first. For the three books and their separate paperback and Kindle options, choose the exam you are preparing for.

The books are separate purchases. This calculator does not test exam readiness or replace conductor ampacity, termination, protection or local requirements.

★ Resources
Scroll to Top
Not a licensed Professional Engineer in Texas or any U.S. state. Does not offer engineering services. Exam-prep education only.