NEC 690 PV Calculations for Apprentices: Cold-Weather String Voltage, the 125% Current Factors and Rapid Shutdown Limits

Updated About 5 min read

Short answer: PV voltage is highest on the coldest morning, so the maximum string voltage is the sum of the module open-circuit voltages corrected for the lowest expected temperature (NEC 690.7(A)). PV current is figured as 125% of the short-circuit current (NEC 690.8(A)(1)), and conductors without adjustment are then sized at another 125%, for 156.25% in total (NEC 690.8(B)(1)). An inverter’s output breaker is at least 125% of its continuous output current. Rapid shutdown lowers the voltage on the controlled PV conductors on or in buildings within 30 seconds, with limits that depend on where the conductor is relative to the array. It does not make every PV part safe to touch.

PSI lists photovoltaics in the Renewable Energy Technologies subject area of the Texas Journeyman exam: 2 scored NEC Knowledge questions and 1 scored Calculations question. PSI does not say how many cover PV calculations alone. The Texas Journeyman Practice Pack has 1,000 original questions and 10 timed mock exams in the real two-part format, with step-by-step solutions for every calculation. Try free practice questions without signing up. Get the full pack for US$39 with one payment.

Tsai Electro is an independent learning site. Not affiliated with TDLR, PSI or NFPA. We explain the ideas in our own words and do not reproduce NEC text. Check every rule and table value in your own 2026 NEC, and follow your supervisor and the local inspector.

Calculation 1: maximum string voltage

A PV module’s open-circuit voltage (Voc) is printed at standard test conditions, 25°C. As the cells get colder, the voltage goes up. The code gives two ways to correct for the lowest expected ambient temperature:

  • Module temperature coefficient. Use the voltage temperature coefficient from the module’s instructions (NEC 690.7(A)(1)).
  • Table method for crystalline silicon modules. Multiply by the factor from Table 690.7(A), which rises above 1.00 as the temperature falls (NEC 690.7(A)(2)).

Worked example, table method. Crystalline silicon modules with Voc = 40.0 V. The lowest expected temperature is -8°C, so the factor from Table 690.7(A) is 1.14. The system is on a one-family dwelling, where PV dc circuits are limited to 600 V.

  1. Corrected Voc per module: 40.0 × 1.14 = 45.6 V.
  2. Maximum modules in series: 600 ÷ 45.6 = 13.2, so 13 modules. Always round down.
  3. String voltage: 13 × 45.6 = 592.8 V.

Same modules, coefficient method. The instructions list a Voc coefficient of -0.28% per °C.

  1. Temperature difference: 25 – (-8) = 33°C.
  2. Correction: 1 + (0.0028 × 33) = 1.0924.
  3. Corrected Voc: 40.0 × 1.0924 = 43.696 V, and 13 modules give 13 × 43.696 = 568.0 V. Keep the unrounded value until the last step.

The two methods give different answers. On an exam, use the method the question names. The installer must post the highest maximum dc voltage on a permanent label at the dc PV disconnecting means, the electronic power conversion equipment or the associated distribution equipment (NEC 690.7(D)).

Calculation 2: current and conductors

  1. Maximum circuit current. For one string, 125% of the module short-circuit current (Isc). Where modules or strings are in parallel, add their Isc values first, then apply 125% (NEC 690.8(A)(1)).
  2. Conductor without adjustment. At least 125% of that maximum current (NEC 690.8(B)(1)). 1.25 × 1.25 = 1.5625, so 156.25% of Isc.
  3. Conductor with adjustment and correction. After temperature correction and bundling adjustment, the ampacity must still be at least the maximum circuit current from step 1 (NEC 690.8(B)(2)). Choose a conductor that passes both the step 2 check and this check.

Worked example. One string of modules with Isc = 13.0 A.

  1. Maximum current: 13.0 × 1.25 = 16.25 A.
  2. Without adjustment: 16.25 × 1.25 = 20.3125 A, so the conductor needs at least that much ampacity.
  3. On a hot roof the conductor ampacity after correction and adjustment must still be at least 16.25 A.

Calculation 3: inverter output breaker

The inverter output circuit current is the inverter’s continuous output current rating (NEC 690.8(A)(1)(c)). The overcurrent device must be at least 125% of it (NEC 690.9(B)(1)).

An inverter has a continuous output rating of 24 A: 24 × 1.25 = 30 A minimum, which is a standard size.

Safety rules that come with the numbers

  • Arc-fault protection. PV dc circuits at 80 V dc or more need listed PV arc-fault protection, with a limited exception (NEC 690.11).
  • Rapid shutdown. Outside the array boundary, controlled conductors drop to not more than 30 V within 30 seconds. Inside the boundary, one option limits them to not more than 80 V within 30 seconds (NEC 690.12). A permanent label states that the system has rapid shutdown (NEC 690.12(D)).
  • Ground-fault protection. PV dc circuits over 30 V or 8 A need listed ground-fault detection and interruption (NEC 690.41(B)).
  • Wiring. Exposed single conductors in the array are PV wire or other listed types (NEC 690.31(C)(1)), and dc wiring methods on or in buildings are marked at intervals of not more than 10 feet (NEC 690.31(D)(2)).
  • Connectors. Readily accessible connectors over 30 V dc must be the latching or locking type that takes a tool to open (NEC 690.33(C)).

Check yourself

  1. Why does PV voltage rise in winter? Colder cells produce a higher open-circuit voltage.
  2. A string has Isc = 10 A. What is the minimum conductor ampacity without adjustment? 10 × 1.5625 = 15.625 A.
  3. An inverter is rated 40 A continuous output. What is the minimum breaker? 40 × 1.25 = 50 A.

Disclosure: If you buy through the Amazon link below, Tsai Electro may earn a commission at no extra cost to you. As an Amazon Associate I earn from qualifying purchases.

Find Article 690 faster on exam day

NFPA 70, National Electrical Code, 2026 Edition (softcover). Highlight Table 690.7(A), the two 125% steps in 690.8 and the rapid shutdown limits in 690.12, and practice going from the table to the multiplication quickly. The Texas exam is open book. PSI allows a soft-bound NEC with highlighting, underlining and notes made in advance. Loose-leaf, spiral-bound and ring-bound copies are not allowed, and only permanent index tabs made or supplied by the NEC publisher are permitted; homemade and third-party tabs are not.

FAQ

How do you calculate maximum PV string voltage?

Add the open-circuit voltages of the modules in series, corrected for the lowest expected ambient temperature with the module’s temperature coefficient or, for crystalline silicon modules, Table 690.7(A).

Where does 156.25% come from in solar calculations?

The maximum circuit current is 125% of the short-circuit current, and conductors without adjustment are sized at 125% of that. 1.25 × 1.25 = 1.5625.

What voltage does rapid shutdown require?

Outside the array boundary, not more than 30 V within 30 seconds. Inside the boundary, one option is not more than 80 V within 30 seconds.

Are PV calculations on the Texas Journeyman exam?

PSI lists photovoltaics in Renewable Energy Technologies: 2 scored NEC Knowledge questions and 1 scored Calculations question.

Next step: practice PV and renewable energy questions under timed exam conditions. The Texas Journeyman Practice Pack has 10 timed mock exams in the two-part format, 59 questions in 130 minutes and 26 in 110 minutes, with step-by-step solutions for every calculation. 1,000 questions, free questions to try first with no sign-up, US$39, one payment.

Next skill: interconnection and energy storage. See how the inverter output connects to the building: NEC 705 and 706 interconnection and energy storage.

Sources checked October 2026