NEC 342 IMC and 360 Flexible Metallic Tubing for the Journeyman Exam: Where Each Is Allowed, Sizes, Bends and the 6-Foot Limit

Updated About 6 min read

Short answer: Intermediate metal conduit (IMC) is a threadable steel conduit with a thinner wall than rigid metal conduit. It is allowed in all atmospheric conditions and occupancies, in concrete, in wet locations and where exposed to severe physical damage, with corrosion protection where the conditions call for it (NEC 342.10). Trade sizes run from 1/2 through 6 (NEC 342.20), a run between pull points has no more than 360 degrees of bends (NEC 342.26), and it is generally fastened within 3 feet of each termination and supported at intervals of not more than 10 feet, with the exceptions the article lists (NEC 342.30). Flexible metallic tubing (FMT) is a liquidtight, flexible metal tubing without a nonmetallic jacket. It is limited to dry, accessible locations on branch circuits (NEC 360.10), trade sizes 1/2 and 3/4, with 3/8 allowed in limited cases (NEC 360.20), and it cannot be used in lengths over 6 feet (NEC 360.12(6)).

PSI lists Wiring Methods and Materials (10 scored NEC Knowledge and 2 scored Calculations questions) as a subject area of the Texas Journeyman exam. PSI does not name Article 342 or 360 or say how many questions cover them. The Texas Journeyman Practice Pack has 1,000 original questions and 10 timed mock exams in the real two-part format, with step-by-step solutions for every calculation. Try free practice questions without signing up. Get the full pack for US$39 with one payment.

Tsai Electro is an independent learning site. Not affiliated with TDLR, PSI or NFPA. We explain the ideas in our own words and do not reproduce NEC text. Check every rule and table value in your own 2026 NEC, and follow your supervisor and the local inspector.

Why these two show up on the exam

Most raceway questions are about EMT, PVC and rigid metal conduit, covered on NEC 344, 352 and 358 raceway installation rules. IMC and FMT are tested because they look like their better-known cousins but have their own article and their own limits. The usual traps: thinking IMC cannot go where rigid conduit goes, and thinking FMT is the same as flexible metal conduit.

ItemIMC (Article 342)FMT (Article 360)
What it isRigid steel conduit, threadable, thinner wall than RMCFlexible, liquidtight metal tubing, no jacket
Where it can goAll atmospheric conditions and occupancies, concrete, wet locations, severe physical damageDry, accessible locations, branch circuits, 1000 volts or less
Trade sizes1/2 through 61/2 and 3/4; 3/8 in limited uses
Length limitNone in the articleNot over 6 feet
Bends360 degrees total between pull pointsBend radius from the tables in the article

IMC: the rules that get tested

  • Uses permitted. All atmospheric conditions and occupancies, in concrete and in direct contact with the earth with corrosion protection where needed, in wet locations, and where subject to severe physical damage (NEC 342.10).
  • Dissimilar metals. Where practicable, avoid contact between dissimilar metals in the run so galvanic action does not eat the conduit (NEC 342.14).
  • Size. Trade size 1/2 is the smallest and trade size 6 is the largest (NEC 342.20). Whether a large size is easy to buy is a separate question from what the code allows.
  • Fill. The number of conductors follows the conduit fill tables in Chapter 9 (NEC 342.22).
  • Bends. Made without damage and without reducing the inside diameter (NEC 342.24), and no more than the equivalent of four quarter bends, 360 degrees total, between pull points (NEC 342.26).
  • Reaming. Cut ends are reamed to remove rough edges (NEC 342.28).
  • Securing and supporting. Generally fastened within 3 feet of each outlet box, junction box, device box, cabinet, conduit body or other termination, and supported at intervals of not more than 10 feet (NEC 342.30). The section has exceptions, including longer securing distances where structural members do not allow 3 feet and longer support spacing for straight runs with threaded couplings under the rigid metal conduit support table. Read the exception that fits the question instead of applying 3 and 10 feet everywhere.
  • Couplings and connectors. Couplings and connectors are made up tight. Fittings used in concrete or masonry are listed for concrete-tight use, and fittings used in wet locations are listed for wet locations (NEC 342.42). Check the 2026 wording of this section in your own code book, because it was revised.

FMT: the rules that get tested

  • Uses permitted. Branch circuits, in dry locations, where concealed, in accessible locations, at 1000 volts or less (NEC 360.10).
  • Uses not permitted. Not in hoistways, storage battery rooms, hazardous locations unless another article allows it, underground or embedded in concrete, where subject to physical damage, and not in lengths over 6 feet (NEC 360.12).
  • Size. Trade sizes 1/2 and 3/4. Trade size 3/8 is allowed in the same limited uses where 3/8 flexible metal conduit is allowed (NEC 360.20).
  • Fill. Trade sizes 1/2 and 3/4 follow the Chapter 9 fill tables; trade size 3/8 follows the small-conduit table used for flexible metal conduit (NEC 360.22).
  • Bends. Where the tubing will flex during use, the bend radius follows one table; where bends are fixed during installation, it follows another (NEC 360.24(A)).

Whether FMT can serve as the equipment grounding conductor depends on its length, its fittings and the circuit rating. That rule lives in Article 250 with the other flexible raceways.

Worked example: bends in an IMC run

An IMC run leaves a panel with a 90-degree bend, has two 45-degree offsets made of two 45-degree bends each, and enters a pull box with another 90-degree bend.

  1. Add the bends. 90 + (45 + 45) + (45 + 45) + 90 = 360 degrees.
  2. Check the limit. 360 degrees is the maximum between pull points, so the run is at the limit.
  3. Add one more bend? A third offset would add 90 degrees and bring the total to 450 degrees. You would need a pull point, such as a conduit body or pull box, to split the run.

Worked example: FMT length

A luminaire whip in a dry, accessible ceiling space needs 7 feet of flexible metallic tubing.

  1. Check the length limit. FMT cannot be used in lengths over 6 feet.
  2. Result. 7 feet is not allowed. Shorten the run to 6 feet or less, or use a different wiring method that the job and the other articles allow.

Check yourself

  1. Can IMC be installed where it is exposed to severe physical damage? Yes.
  2. What is the largest trade size of IMC? Trade size 6.
  3. Can FMT be installed underground? No.
  4. A run has three 90-degree bends and one 45-degree bend. How many degrees remain before the limit? 360 − 315 = 45 degrees.

Disclosure: If you buy through the Amazon link below, Tsai Electro may earn a commission at no extra cost to you. As an Amazon Associate I earn from qualifying purchases.

Keep IMC and FMT separate in your NEC

NFPA 70, National Electrical Code, 2026 Edition (softcover). Write “3 ft, 10 ft, see exceptions” next to 342.30, “dry, accessible” next to 360.10 and “6 ft max” next to 360.12, so the two articles do not blur with 344 and 348 under time pressure. The Texas exam is open book. PSI allows a soft-bound NEC with highlighting, underlining and notes made in advance. Loose-leaf, spiral-bound and ring-bound copies are not allowed, and only permanent index tabs made or supplied by the NEC publisher are permitted; homemade and third-party tabs are not.

FAQ

Is IMC allowed everywhere rigid metal conduit is allowed?

IMC is allowed in all atmospheric conditions and occupancies, in concrete, in wet locations and where exposed to severe physical damage. Check the specific article for any special location before you swap one for the other.

How far apart are IMC supports?

Fastened within 3 feet of each termination and supported at intervals of 10 feet or less, with longer spacing for some straight threaded runs.

What is the maximum length of flexible metallic tubing?

6 feet.

Can flexible metallic tubing be used in wet locations?

No. FMT is limited to dry locations.

How many degrees of bends are allowed in an IMC run?

No more than 360 degrees total between pull points.

Next step: practice wiring method questions under timed exam conditions. The Texas Journeyman Practice Pack has 10 timed mock exams in the two-part format, 59 questions in 130 minutes and 26 in 110 minutes, with step-by-step solutions for every calculation. 1,000 questions, free questions to try first with no sign-up, US$39, one payment.

Next skill: flexible conduit and grounding. See when a flexible raceway can be the equipment grounding conductor: NEC 250.118, 348 and 350 flexible conduit grounding.

Sources checked October 2026