Weekly electrician practice: box-fill worked example

TSAI ELECTRO | WEEKLY PRACTICE 01

How much box volume is enough?

Six insulated 12 AWG conductors enter a box and are spliced or terminated. It contains one single-gang device yoke connected to 12 AWG conductors, internal clamps and four entering 12 AWG equipment grounding conductors. There are no support fittings, terminal-block assemblies or long loops. What minimum volume do these fill allowances require?

A 18.00 in³   B 20.25 in³
C 22.50 in³   D 27.00 in³

Check your answer and the counting steps

C: 22.50 cubic inches.

  1. Six insulated conductors: 6 allowances.
  2. One single-gang yoke: 2 allowances, using its largest connected conductor.
  3. All internal clamps together: 1 allowance.
  4. Four entering equipment grounds: 1 allowance, using the largest entering ground.

(6 + 2 + 1 + 1) × 2.25 = 22.50 in³.

NEC 2026: 314.16(B)(1), (B)(2), (B)(4), (B)(5) and Table 314.16(B)(4). The question intentionally uses one conductor size; different sizes and other fittings need their own checks.

Original study question; no official exam item is reproduced. Check the complete rule and local requirements. Official NFPA reader.