NEC 120.83 and 120.84 for the Journeyman Exam: Existing Dwelling Additions and the Multifamily Optional Method

Updated About 7 min read

Short answer: In the 2026 NEC, load calculations moved from Article 220 to Article 120, so the old 220.83 to 220.88 optional calculations are now in Part IV of Article 120. For an existing dwelling unit (NEC 120.83), the 2026 edition uses one table: the first 8 kVA of existing and new load at 100 percent, the remainder of the existing load at 40 percent, new EVSE and new central electric resistance space heating at 80 percent, and other new loads, such as a heat pump, at 50 percent. General lighting in these calculations is 2 VA per square foot, down from 3 VA. For three or more dwelling units on one service or feeder (NEC 120.84), add the connected load of every unit and multiply by one demand factor from a table that drops as the number of units rises. Under 120.87, a qualifying existing installation may use its maximum measured demand over one year, taken at 125 percent, plus the new load, when the section’s other conditions are met.

PSI lists Services, Service Equipment and Separately Derived Systems (6 scored NEC Knowledge and 4 scored Calculations questions) and Feeders (3 and 3) as subject areas of the Texas Journeyman exam, and names load calculations under Services. PSI does not say how many questions use the optional methods. The Texas Journeyman Practice Pack has 1,000 original questions and 10 timed mock exams in the real two-part format, with step-by-step solutions for every calculation. Try free practice questions without signing up. Get the full pack for US$39 with one payment.

Tsai Electro is an independent learning site. Not affiliated with TDLR, PSI or NFPA. We explain the ideas in our own words and do not reproduce NEC text. Check every rule and table value in your own 2026 NEC, and follow your supervisor and the local inspector.

Where this fits

The standard method and the single dwelling optional method are on the service and feeder load calculations page. This page covers the other optional calculations in the same part of Article 120:

SectionUse it when
120.83You add load to one existing dwelling unit and need to know if the service or feeder can carry it
120.84Three or more dwelling units share one service or feeder
120.85Two dwelling units share one feeder
120.86A school building service or feeder
120.87The existing load can come from measured demand instead of a calculation
120.88A new restaurant service or feeder

On exam day, the hard part is choosing the method. Read the question for “existing”, “three or more units”, “school” or “restaurant”, then go to that section.

120.83: adding load to an existing dwelling

The method is for an existing dwelling unit served by a 120/240 V or 208Y/120 V, 3-wire service or feeder. Start with the existing connected load: general lighting and general-use receptacles at 2 VA per square foot, 1,500 VA for each 20 ampere small appliance and laundry circuit, and the nameplate rating of the fixed appliances, ranges, ovens, dryers and water heaters.

LoadPercent in Table 120.83
First 8 kVA of existing and new load100 percent
Existing load, remainder40 percent
New EVSE80 percent
New central electric resistance space heating80 percent
All other new loads, including heat pumps50 percent

The 2023 edition split the method by whether the new load was air conditioning or space heating and counted that load at 100 percent. The 2026 table replaces that split, so older study guides give a different answer. In the examples below the existing load alone is more than 8 kVA, so the first 8 kVA is covered by existing load and each new load is counted at its own row’s percentage. Add the applicable loads and convert the total to amperes. Compare the result with the existing service or feeder rating, then check the conductor and overcurrent protection requirements before concluding that the addition can be supplied. Check the exact rows and notes of Table 120.83 in your code book.

Worked example: an EV charger or an electric furnace on a 100 A service

A 1,800 square foot house has a 100 A, 120/240 V service, gas heat and no air conditioning.

Existing load.

  1. Lighting. 1,800 × 2 = 3,600 VA.
  2. Small appliance and laundry circuits. 3 × 1,500 = 4,500 VA.
  3. Appliances. 12 kW range + 5 kW dryer + 4.5 kW water heater = 21,500 VA.
  4. Existing total. 3,600 + 4,500 + 21,500 = 29,600 VA.
  5. Table 120.83. 8,000 + (29,600 – 8,000) × 0.40 = 8,000 + 8,640 = 16,640 VA.

Option A: a new 7,200 VA EVSE (30 A at 240 V).

  1. 7,200 × 0.80 = 5,760 VA.
  2. 16,640 + 5,760 = 22,400 VA, and 22,400 ÷ 240 = 93.3 A. The calculated load is below the 100 A service rating, so the addition is supported by this load calculation. The installation still has to meet the conductor, overcurrent protection and EVSE requirements.

Option B: a new 10 kW central electric furnace instead.

  1. 10,000 × 0.80 = 8,000 VA.
  2. 16,640 + 8,000 = 24,640 VA, and 24,640 ÷ 240 = 102.7 A. The calculated load exceeds the 100 A service rating, so this furnace cannot be supported under the example’s assumptions without reducing the calculated load or increasing the service capacity. A different heating system needs its own calculation.

120.84: the multifamily optional method

The method can be used when all of these are true:

  • Three or more dwelling units are on the same service or feeder.
  • No dwelling unit is supplied by more than one feeder.
  • Each unit has electric cooking equipment, and electric space heating or air conditioning or both. For units without electric cooking, an exception lets you compare the standard calculation with this method using an assumed 8 kW of cooking per unit and use the lesser result.

For each unit, include general lighting and general-use receptacles at 2 VA per square foot, 1,500 VA for each required small appliance and laundry circuit, the nameplate loads of appliances and cooking equipment, clothes dryers as 120.84 specifies, permanently connected motor loads not otherwise included, and the larger of the air conditioning or fixed electric space heating load. Then add all units together and apply one demand factor from the multifamily table.

Number of dwelling unitsDemand factor
3 to 545 percent
6 and 744 percent
8 to 1043 percent
12 and 1341 percent
24 and 2535 percent
62 and over23 percent

This is part of the table. The full table uses ranges of unit counts, with some counts listed on their own rows. Find the row that covers the number of units in the question and use that row’s factor. House loads such as hallway lighting, laundry rooms and pumps are calculated separately with the standard method and added after the demand factor.

Worked example: a 10 unit building

Ten identical units, each 1,000 square feet, with a 12 kW range, a 5 kW dryer, a 4.5 kW water heater, a 1.2 kW dishwasher, a 7 kW electric heater and a 3.6 kVA air conditioner. The service is 120/240 V single phase. There are no house loads in this example.

  1. Lighting. 1,000 × 2 = 2,000 VA.
  2. Small appliance and laundry circuits. 3 × 1,500 = 4,500 VA.
  3. Appliances. 12,000 + 5,000 + 4,500 + 1,200 = 22,700 VA.
  4. Heating or cooling, larger value. 7,000 VA heat is larger than 3,600 VA air conditioning: 7,000 VA.
  5. Connected load per unit. 2,000 + 4,500 + 22,700 + 7,000 = 36,200 VA.
  6. All units. 36,200 × 10 = 362,000 VA.
  7. Demand factor for 10 units. 43 percent: 362,000 × 0.43 = 155,660 VA.
  8. Amperes. 155,660 ÷ 240 = 648.6 A calculated load.

The neutral is calculated separately under the standard method rules; this method sizes the ungrounded conductors.

120.85 to 120.87 in one line each

  • Two dwelling units (120.85). If the standard calculation for two units comes out higher than the optional calculation for three identical units, the lesser of the two may be used (NEC 120.85).
  • Schools (120.86). An optional method based on load per square foot with stepped demand factors.
  • Existing loads from measured demand (120.87). Use the highest demand recorded over one year, or a continuous recording over at least 30 days under the stated conditions, at 125 percent, then add the new load. The result still has to fit the conductors and the overcurrent protection.

Check yourself

  1. Which Article holds the dwelling load calculations in the 2026 NEC? Article 120.
  2. In Table 120.83, what percent applies to a new EVSE? 80 percent. The first 8 kVA of existing and new load is 100 percent, and the rest of the existing load is 40 percent.
  3. What is the minimum number of units for the multifamily optional method? Three.
  4. In the multifamily method, are house loads part of the demand factor? No. They are calculated separately and added.

Disclosure: If you buy through the Amazon link below, Tsai Electro may earn a commission at no extra cost to you. As an Amazon Associate I earn from qualifying purchases.

Mark the optional methods in your permitted NEC copy

NFPA 70, National Electrical Code, 2026 Edition (softcover). Write “first 8 kVA at 100, rest of existing at 40; new EVSE or resistance heat 80; other new 50” and “3+ units: one factor from the table” next to Part IV of Article 120 so you choose the method fast. The Texas exam is open book. PSI allows a soft-bound NEC with highlighting, underlining and notes made in advance. Loose-leaf, spiral-bound and ring-bound copies are not allowed, and only permanent index tabs made or supplied by the NEC publisher are permitted; homemade and third-party tabs are not.

FAQ

Where did 220.83 and 220.84 go in the 2026 NEC?

Load calculations moved to Article 120. The existing dwelling and multifamily optional calculations are 120.83 and 120.84.

How is new load added to an existing dwelling?

The first 8 kVA of existing and new load is taken at 100 percent and the rest of the existing load at 40 percent. New EVSE and new central electric resistance heat are added at 80 percent, and other new loads at 50 percent.

When can the multifamily optional method be used?

For three or more dwelling units on one service or feeder, with no unit supplied by more than one feeder and the equipment conditions of the section met.

Are house loads included in the multifamily demand factor?

No. House loads are calculated with the standard method and added separately.

Can measured demand replace the calculated existing load?

Yes, for a qualifying existing installation when the section’s other conditions are met. The maximum measured demand over one year is taken at 125 percent and the new load is added.

Next step: practice load calculations under timed exam conditions. The Texas Journeyman Practice Pack has 10 timed mock exams in the two-part format, 59 questions in 130 minutes and 26 in 110 minutes, with step-by-step solutions for every calculation. 1,000 questions, free questions to try first with no sign-up, US$39, one payment.

Next skill: service and feeder load calculations. Work the standard method and the single dwelling optional method step by step: service and feeder load calculations.

Sources checked October 2026