NEC Article 240 Fuses and Circuit Breakers for the Journeyman Exam: Plug Fuses, Type S, Interrupting Ratings and Slash-Rated Breakers

Updated About 7 min read

Short answer: Plug fuses are used only on circuits of 125 V or less between conductors, or on systems with a grounded neutral point where no conductor is more than 150 V to ground (NEC 240.50). Edison-base plug fuses are used only as replacements in existing installations with no evidence of overfusing or tampering (NEC 240.51), and a Type S fuse fits only a matching nonremovable adapter, which locks the fuseholder to one size class (NEC 240.53). A cartridge fuse is marked with its interrupting rating when that rating is other than 10,000 A (NEC 240.60), and a circuit breaker when its rating is other than 5,000 A (NEC 240.83). A slash-rated breaker such as 120/240 V is used only on a solidly grounded system where no conductor exceeds the lower value to ground and the higher value between conductors (NEC 240.85).

PSI lists Branch Circuits and Conductors (10 scored NEC Knowledge and 4 scored Calculations questions) and Services, Service Equipment and Separately Derived Systems (6 and 4) as subject areas of the Texas Journeyman exam, and names branch circuits and their overcurrent protection in them. PSI does not say how many questions cover fuses and breakers. The Texas Journeyman Practice Pack includes 1,000 original questions and 10 timed mock exams in the real two-part format, plus step-by-step solutions for every calculation. You can try free practice questions with no sign-up. The full pack is US$39, paid once.

Tsai Electro is an independent learning site. Not affiliated with TDLR, PSI or NFPA. We explain the rules in plain language and do not copy NEC text. Check every rule and table value in your own 2026 NEC, and follow your supervisor and the local inspector.

The devices, not the sizing

240.4, the standard sizes in 240.6 and where protection goes are on the services and overcurrent protection page. Here we look at the fuses and breakers themselves: fuse types, breaker markings, and how to tell whether a breaker is rated for the system in front of you.

Plug fuses (240.50 to 240.54)

ItemRule
Voltage125 V or less between conductors, or a grounded system where no conductor exceeds 150 V to ground
ShapePlug fuses of 15 A and lower have a hexagonal window, cap or other prominent part, so they can be told apart by sight
Screw shellThe screw shell of a plug fuseholder is connected to the load side of the circuit
Edison baseReplacements only, in existing installations with no evidence of overfusing or tampering
Type S classes0 to 15 A, 16 to 20 A, and 21 to 30 A. A fuse from a higher class cannot fit a holder for a lower class
Type S adaptersFit Edison-base fuseholders, are designed to be nonremovable once installed, and are made so they cannot be easily altered

Why Type S exists: an Edison-base holder takes a 30 A fuse just as easily as a 15 A one, even on 14 AWG copper that generally needs 15 A protection. A Type S adapter screws in once and then accepts only its own size class.

Cartridge fuses (240.60, 240.61)

  • 300 V type. A 300 V cartridge fuse or fuseholder is used only on circuits of 300 V or less between conductors, or on single-phase line-to-neutral circuits supplied from a 3-phase, 4-wire, solidly grounded neutral source where the line-to-neutral voltage does not exceed 300 V.
  • Noninterchangeable. Fuseholders are designed so it is difficult to put a fuse of a given class into a holder designed for a lower current or a higher voltage than that class. Fuseholders for current-limiting fuses do not accept fuses that are not current-limiting.
  • Marking. Cartridge fuses are marked with ampere rating, voltage rating, interrupting rating when it is other than 10,000 A, current limiting where applicable, and the manufacturer.
  • Classification. Fuses are classified by the listing, such as Class H, K, R, J, T, G, CC and L. Class R holders reject fuses that are not Class R.

Circuit breakers (240.80 to 240.87)

  • Trip free and manual operation. A breaker can be closed and opened by hand, and it trips even if the handle is held closed.
  • ON is up. Where breaker handles are operated vertically, the up position is ON.
  • Not easily changed. The trip setting or time needed to operate cannot be changed without dismantling the breaker or breaking a seal, except where adjustable by design and accessible only to qualified persons.
  • Markings. The ampere rating is durably marked and visible after installation. The interrupting rating is marked when it is other than 5,000 A. Breakers used as switches in 120 V and 277 V fluorescent lighting circuits are listed and marked SWD or HID; breakers used as switches in HID lighting circuits are marked HID.
  • Supplementary protection. Supplementary overcurrent devices, such as fuses inside a luminaire, cannot replace the required branch-circuit overcurrent protection (240.10). They do not have to be readily accessible, under the supplementary-device provision in 240.24.

Interrupting rating versus ampere rating

The ampere rating is the device’s rated current. A breaker does not trip the instant current goes past that number; how long it takes depends on how far over the rating the current is and on the breaker’s trip curve. The interrupting rating is the most fault current it can safely open. A 20 A breaker with a 10,000 A interrupting rating installed where 22,000 A of fault current is available can fail violently during a short circuit. An overcurrent device needs an interrupting rating at least equal to the available fault current at its line terminals, unless it is part of a series-rated combination allowed by 240.86.

Series ratings (240.86). A downstream breaker can be used where the available fault current is above its own interrupting rating when the combination meets 240.86. Normally that means a tested series-rated combination, identified and marked on the equipment, using only the identified devices. The section also limits motor contribution between the two devices. For existing installations, the section also allows an engineered series rating selected under the supervision of a licensed professional engineer, with its own documentation and field marking.

Slash ratings (240.85)

Breaker ratingSystemOK?
120/240 V120/240 V single-phase, 3-wireYes
120/240 V208Y/120 V, 3-phase, 4-wireYes, on a solidly grounded 208Y/120 V system. 120 V to ground and 208 V between conductors are both within the ratings
120/240 V240 V high-leg delta, circuit that uses the high legNo. The high leg is about 208 V to ground, above the 120 V slash
120/240 V240 V high-leg delta, circuit on the two 120 V legs onlyYes. Neither conductor is more than 120 V to ground
480Y/277 V480 V ungrounded or corner-grounded deltaNo. Use a breaker with a straight 480 V rating
Straight 240 VSystem with no more than 240 V between conductorsYes, when the breaker’s listing and pole configuration fit the application

Arc energy reduction (240.87)

If a breaker’s highest continuous current trip setting, including the highest setting it can be adjusted to, is 1,200 A or more, 240.87 requires documentation, an approved way to reduce clearing time, and performance testing of that method. Examples include zone-selective interlocking, differential relaying, and an energy-reducing maintenance switch with a local status indicator. Check 240.87 in your NEC for the full list.

Worked example: an old fuse box

A fuse panel in a 1950s house has a 30 A Edison-base fuse in a socket feeding 14 AWG copper. You find no other signs of tampering.

  1. Allowed wire protection: 14 AWG copper is generally limited to 15 A overcurrent protection.
  2. Problem: a 30 A fuse on 14 AWG is overfusing. Edison-base fuses are allowed only as replacements where there is no evidence of overfusing or tampering, so putting another Edison-base fuse in this socket would not meet 240.51.
  3. Correction: first have the fuseholder, wiring and connected loads checked by a qualified electrician. If they are suitable, a 15 A Type S adapter with a matching 15 A Type S fuse keeps a larger fuse out. After the adapter is in, only a 0 to 15 A Type S fuse fits.

Five quick questions

  1. Maximum voltage between conductors for plug fuses on a circuit without a grounded neutral point? 125 V.
  2. Which way is ON for a vertically operated breaker handle? Up.
  3. A 120/240 V slash-rated breaker on a circuit that uses the high leg of a 240 V high-leg delta. OK? No.
  4. Breaker interrupting rating that does not need to be marked? 5,000 A.
  5. Cartridge fuse interrupting rating that does not need to be marked? 10,000 A.

Disclosure: If you buy through the Amazon link below, Tsai Electro may earn a commission at no extra cost to you. As an Amazon Associate I earn from qualifying purchases.

Don’t mix up 5,000 A and 10,000 A

NFPA 70, National Electrical Code, 2026 Edition (softcover). Highlight the 10,000 A in 240.60 and the 5,000 A in 240.83 in the same color, because they are easy to swap under time pressure. The Texas exam is open book. PSI allows a soft-bound NEC with highlighting, underlining and notes made in advance. Loose-leaf, spiral-bound and ring-bound copies are not allowed, and only permanent index tabs made or supplied by the NEC publisher are permitted; homemade and third-party tabs are not.

FAQ

What is a Type S fuse?

A plug fuse with a base that fits only a matching Type S adapter or fuseholder of its size class (0 to 15 A, 16 to 20 A, or 21 to 30 A), so a larger fuse cannot be put in a smaller circuit.

Can I still use Edison-base fuses?

Only as replacements in existing installations where there is no evidence of overfusing or tampering.

What does a 120/240 V slash rating mean?

The breaker is for a solidly grounded circuit where no conductor is more than 120 V to ground and no more than 240 V between conductors. On a 240 V high-leg delta, that rules out any circuit that uses the high leg, and it rules out ungrounded delta systems.

What is the difference between ampere rating and interrupting rating?

They are easy to mix up. The ampere rating is what the breaker or fuse is rated to carry, and it sets the overload protection. The interrupting rating is the highest short-circuit current it can safely open.

Which way is ON on a breaker?

Up, when the handle operates vertically.

Try fuse, breaker and overcurrent questions against the clock. The Texas Journeyman Practice Pack has 10 timed mock exams in the two-part format, 59 questions in 130 minutes and 26 in 110 minutes, with step-by-step solutions for every calculation. 1,000 questions, free questions to try first with no sign-up, US$39, one payment.

Up next: feeder tap rules, for when a smaller conductor can be tapped from a feeder without protection at the tap point: 240.21 feeder taps.

Sources checked October 2026