Short answer: Article 517 covers health care facilities, from hospitals to clinics and dental offices. Patient care spaces are sorted into four categories by the facility. Branch circuits serving patient care spaces need two grounding paths: a metal raceway or cable armor that qualifies as an equipment grounding conductor, plus an insulated copper equipment grounding conductor (NEC 517.13). A general care bed location needs at least 8 receptacles (NEC 517.18) and a critical care bed location at least 14 (NEC 517.19), normally supplied by at least one normal system circuit and at least one critical branch circuit. Operating rooms have their own higher minimum. A hospital’s essential electrical system has three branches: life safety, critical and equipment.
PSI lists Special Occupancies, Equipment and Conditions as a subject area on the Texas Journeyman exam: 6 scored NEC Knowledge questions and 3 scored Calculations questions. PSI does not say how many cover health care facilities. The Texas Journeyman Practice Pack has 1,000 original questions and 10 timed mock exams in the real two-part format, with step-by-step solutions for every calculation. Try free practice questions without signing up. Get the full pack for US$39 with one payment.
Tsai Electro is an independent learning site. Not affiliated with TDLR, PSI or NFPA. We explain the ideas in our own words and do not reproduce NEC text. Check every rule and table value in your own 2026 NEC, follow the project documents and NFPA 99 requirements the facility uses, and follow your supervisor and the local inspector.
Patient care space categories
The facility’s governing body decides the category of each patient care space, and the electrical rules follow from that.
| Category | Typical spaces | Why it matters |
|---|---|---|
| Category 1 (critical care) | Operating rooms, intensive care, emergency treatment | Failure could cause major injury or death |
| Category 2 (general care) | Patient bedrooms, exam rooms | Failure could cause minor injury |
| Category 3 (basic care) | Spaces where failure is not likely to cause injury but can cause patient discomfort | Requirements depend on the space |
| Category 4 (support) | Spaces where failure is not likely to have a physical impact on patient care, often waiting rooms, offices and storage | Not a patient care space for these rules |
On the job, the drawings and the facility tell you the category of each room. You do not choose it.
Redundant grounding
Branch circuits that serve patient care spaces need two separate grounding paths (NEC 517.13):
- The wiring method itself. The branch circuit is installed in a metal raceway, or in a cable whose metallic armor or sheath qualifies as an equipment grounding conductor under 250.118, and the boxes and fittings in that path are metal. Ordinary Type MC with an armor that does not qualify on its own is not enough. Many jobs use Type MC cable listed for health care facilities, often called HCF cable.
- An insulated copper equipment grounding conductor. It runs with the branch circuit conductors and connects to the grounding terminals of receptacles and the metal enclosures and equipment in the patient care vicinity.
If one path is damaged, the other is still there. That is the reason for the rule: in patient care, a lost ground can expose a patient to current through equipment connected to their body.
Receptacles and circuits at the bed
| Bed location | Minimum receptacles | Branch circuits |
|---|---|---|
| General care (Category 2) | 8 (NEC 517.18) | Normally at least one from the critical branch and at least one from the normal system |
| Critical care (Category 1) | 14 (NEC 517.19) | Normally at least one from the critical branch and at least one from the normal system; a critical branch circuit at a critical care bed serves only that bed location |
| Operating room | 36 | Set by its own rule in 517.19 |
The code allows some exceptions to the normal plus critical branch arrangement, for example where the beds are fed from two separate critical branch transfer switches. Check 517.18 and 517.19 before you plan the circuits.
- Hospital grade. Receptacles at general care and critical care bed locations are generally listed hospital grade. They are made to hold a plug firmly and survive heavy use.
- Pediatric areas. Receptacles in pediatric spaces are listed tamper-resistant or use a listed tamper-resistant cover (NEC 517.18).
- Identification. Receptacles and cover plates on the essential electrical system are identified, often with a distinctive color, and many facilities also label the panel and circuit number on each plate.
The essential electrical system
A hospital’s essential electrical system has three branches. Each branch is supplied through transfer switches, and in smaller systems the code allows one transfer switch to serve more than one branch:
- Life safety branch. Egress lighting, exit signs, fire alarm, alarms for medical gas systems and similar loads.
- Critical branch. Task lighting and selected receptacles in patient care spaces, including the critical branch receptacles at each bed.
- Equipment branch. Large equipment needed for patient care and building operation, such as selected heating, ventilating and medical vacuum equipment.
The wiring of the life safety and critical branches is kept independent of all other wiring, except in the places the code allows, such as transfer switches and certain shared enclosures. Check the branch rules in Part III of Article 517.
Worked example: counting receptacles on a nursing unit
A new nursing unit has 6 general care bed locations and 4 critical care bed locations, none of them operating rooms. Find the minimum number of receptacles at the beds.
- General care. 6 beds × 8 receptacles = 48 receptacles.
- Critical care. 4 beds × 14 receptacles = 56 receptacles.
- Total. 48 + 56 = 104 receptacles at the bed locations, as a minimum.
- Circuits. Assume the usual normal system plus critical branch arrangement. Then all 10 bed locations need circuits from both systems, and each critical care bed gets its own critical branch circuit, so plan both systems to reach every bed.
- Check. 48 ÷ 6 = 8 and 56 ÷ 4 = 14, which match the minimums. The design can always add more.
Check yourself
- What are the two grounding paths for a branch circuit in a patient care space? A metal raceway or qualifying cable armor, plus an insulated copper equipment grounding conductor.
- How many receptacles does a critical care bed location need at minimum? 14.
- Name the three branches of a hospital’s essential electrical system. Life safety, critical and equipment.
Disclosure: If you buy through the Amazon link below, Tsai Electro may earn a commission at no extra cost to you. As an Amazon Associate I earn from qualifying purchases.
Find Article 517 faster on exam day
NFPA 70, National Electrical Code, 2026 Edition (softcover). Highlight the grounding rules in 517.13 and the bed receptacle counts in 517.18 and 517.19, since health care questions often turn on one number. The Texas exam is open book. PSI allows a soft-bound NEC with highlighting, underlining and notes made in advance. Loose-leaf, spiral-bound and ring-bound copies are not allowed, and only permanent index tabs made or supplied by the NEC publisher are permitted; homemade and third-party tabs are not.
FAQ
How many receptacles are required at a hospital bed?
At least 8 at a general care bed location and at least 14 at a critical care bed location. Operating rooms have a separate minimum of 36. The circuits normally come from both the normal system and the critical branch, with some exceptions in Article 517.
What is redundant grounding in a hospital?
Branch circuits in patient care spaces need two grounding paths: a metal raceway or qualifying cable armor, and an insulated copper equipment grounding conductor run with the circuit.
Can I use regular MC cable in a patient room?
Only if its armor or sheath qualifies as an equipment grounding conductor and it also contains an insulated copper equipment grounding conductor. Type MC listed for health care facilities is commonly used for this.
Are health care facilities on the Texas Journeyman exam?
PSI lists Special Occupancies, Equipment and Conditions as a subject area, with 6 scored NEC Knowledge questions and 3 scored Calculations questions. PSI does not say how many cover health care facilities.
Sources checked October 2026
- PSI Candidate Information Bulletin, Texas electrician examinations (updated September 15, 2026): https://test-takers.psiexams.com/api/content/bulletin/1682
- NFPA 70, National Electrical Code, 2026 Edition, Articles 250 and 517