Short answer: The Calculations part of the Texas Master Electrician exam has 33 questions in 170 minutes. Three are not scored, so 30 count, and you need 70% on this part by itself: 21 of the 30 scored points. Services and service equipment (8 points) and motors and generators (6 points) carry almost half the part. In TDLR fiscal year 2025, 19.08% of attempts passed, the lowest of all Journeyman and Master exam parts.
Part of Texas Electrician Exams: every Texas license step and exam in one place. For eligibility, fees and the NEC Knowledge part, see the full Texas Master Electrician exam guide.
Choose practice for the right Texas exam
Preparing for Master Calculations? Review the Master pack’s current contents and formats before buying. The Journeyman pack prepares for a different Texas exam.
Still choosing a license route? Start with the free Texas license types guide, then return to the worked examples below with your code book.
The Calculations part in numbers
| Item | Master Calculations |
|---|---|
| Questions on screen | 33 |
| Not scored | 3 |
| Scored points | 30 |
| Time | 170 minutes, about 5.2 minutes per question |
| Pass mark | 70% on this part, which is 21 of 30 scored points |
| Code edition | 2026 NEC |
| Fee | $78 for both parts; $78 to retake one or both |
The NEC Knowledge part is scored separately: 75 questions (5 unscored) in 150 minutes, also 70%. Unused time in one part does not carry over to the other, so a fast Knowledge part buys you nothing on Calculations.
Where the 30 points are
TDLR’s May 12, 2026 staff report lists the Master Calculations points by subject area. Two areas stand out:
- Electrical services and service equipment: 8 points.
- Motors and generators: 6 points.
Together that is 14 of 30, almost half. The other 16 points are spread across the remaining subject areas. Compared with the Journeyman exam, the Master exam goes deeper into services, feeders and motors. If you can only fix one thing before your date, fix services first and motors second.
Why this is the hardest part
| Fiscal year | Attempts | Pass rate |
|---|---|---|
| 2025 | 3,946 | 19.08% |
| 2024 | 3,487 | 19.96% |
These are attempts, retakes included, not people. In fiscal year 2025, Master Calculations passed fewer attempts than either Journeyman part and fewer than Master NEC Knowledge (22.21%). Two years in a row it has stayed at about one pass in five attempts. More periods are on the Texas electrician exam pass rates page.
What changed with the 2026 NEC
The exam is on the 2026 NEC. If you passed your Journeyman exam on the 2023 edition, many locations moved. The biggest one for this part: load calculations were reorganized from Article 220 into a new Article 120. Re-tab and re-learn your book for 2026 before you time yourself. Book rules are the same as for the Journeyman exam: a soft-bound NEC, publisher tabs only, no handbook and no marking during the exam. See NEC code book tabs for the Texas exam.
A plan for the 21 points
- Start with services. Eight points sit there. Work service and feeder load problems until you can find the 2026 article and set up the calculation without searching.
- Then motors and generators. Six more points. Practice finding the right table first, then the arithmetic.
- Practice the real clock. 33 questions in 170 minutes, on its own, after a full Knowledge part if you can. About 5 minutes a question is an average, not a budget for every question; mark long ones and come back.
- Keep a mistake log. For every miss, write the code location and the step you got wrong. Re-solve it a few days later without the solution.
- If you fail, read the subject breakdown on your score report and study those areas before you pay the $78 retake.
Three free worked examples
These three use only basic electrical formulas, so you can check the setup before you add code rules. They are written by Tsai Electro for practice and are not questions from the PSI exam. On the real exam most problems add a code step, such as a demand factor or a table lookup, on top of arithmetic like this.
Example 1: single-phase load current
Problem. A 9,600 W resistive heater is connected to a 240 V single-phase circuit. What current does it draw?
Formula. I = P / V
Answer. I = 9,600 / 240 = 40 A.
Where people go wrong. Dividing by 120 V instead of the circuit voltage gives 80 A, double the real current. Read the nameplate voltage and the circuit voltage before you divide.
Example 2: three-phase load current
Problem. A balanced 30,000 W resistive load is supplied at 208 V, three-phase. What is the line current?
Formula. I = P / (1.732 x V), where 1.732 is the square root of 3
Answer. I = 30,000 / (1.732 x 208) = 30,000 / 360.3 = about 83.3 A.
Where people go wrong. Leaving out 1.732 gives about 144.2 A. Multiplying the voltage by 3 instead of 1.732 gives about 48.1 A. Both answers often appear among the choices.
Example 3: voltage drop on a two-wire circuit
Problem. A 120 V two-wire circuit carries 20 A. Each conductor, from the panel to the load, has a resistance of 0.1 ohm. What is the voltage drop, and what voltage reaches the load?
Formula. VD = I x R for each conductor, and the current flows out and back, so VD = 2 x I x R
Answer. VD = 2 x 20 x 0.1 = 4 V. The load sees 120 – 4 = 116 V, a drop of about 3.3 percent.
Where people go wrong. Counting only one conductor gives 2 V. On a two-wire circuit the current goes through both conductors, so both resistances count.
Write each miss in your mistake log the same way: the formula, the step you got wrong, and the corrected answer.
ET Member saves your mistake log as member steps you can come back to, alongside the full Texas route: see what ET Member includes.
Practice in the same format
Try 20 free Texas Master questions on the 2026 NEC, no sign-up.
The Texas Master practice pack, US$79 has 368 original practice questions and 10 full two-part timed mocks in the PSI format: NEC Knowledge (75 questions, 150 minutes) and Calculations (33 questions, 170 minutes), each scored against the 70% pass line. Every calculation question comes with a step-by-step solution. One payment, no subscription. Ask within 30 days of payment for a full refund if you have not started a paid mock or downloaded the PDF.
FAQ
How many calculation questions are on the Texas Master Electrician exam?
33, of which 30 are scored. You have 170 minutes for this part.
How many do I need right to pass the Master Calculations part?
70% of the 30 scored points, which is 21. The 3 unscored questions do not count, and you cannot tell which ones they are.
Which topics are worth the most on Master Calculations?
Electrical services and service equipment (8 points) and motors and generators (6 points), per TDLR’s May 12, 2026 staff report.
Can a strong NEC Knowledge score make up for a weak Calculations score?
No. Each part is scored on its own and each needs 70%.
Next step on the Texas ladder: after the Master license, a contractor business needs a Master Electrician of record. See the Texas electrical contractor license.
Sources
- TDLR: Apply for a New Master Electrician License, read October 1, 2026
- PSI candidate information bulletin for TDLR electricians, updated September 15, 2026, read October 1, 2026
- TDLR staff reports, May 12, 2026, read October 1, 2026
- TDLR fiscal year 2025 electrician exam statistics, read October 1, 2026
- TDLR fiscal year 2024 electrician exam statistics, read October 2, 2026
Tsai Electro is an independent learning site, not affiliated with TDLR or PSI. Rules and fees can change, so confirm on the TDLR and PSI pages above.
Why applying 35% to the whole load loses the first band
In the 2026 NEC standard-method dwelling example in Texas Master Electrician Exam Prep, Chapter 4, the supplied general connected load is 8,500 VA: 4,000 VA general lighting, 3,000 VA small-appliance circuits and 1,500 VA laundry. For this worked example, retain the first 3,000 VA at 100% and apply 35% to the remaining 5,500 VA.
3,000 + (8,500 − 3,000) × 0.35 = 4,925 VA.
- 2,975 VA: 8,500 × 0.35 incorrectly discounts the first 3,000 VA too.
- 8,500 VA: keeps the connected value without the example’s demand calculation.
- 4,925 VA: is only this general-load subtotal, not the entire dwelling service load.
The complete example also includes 5,550 VA appliance demand, 5,000 VA dryer load and 8,000 VA for the larger heating or air-conditioning load. Total: 23,475 VA; at the supplied 240 V, 23,475 ÷ 240 = 97.8125 A, shown as 97.8 A. Keep the subtotals separate before combining them.
Read all givens, conditions and the full 2026 NEC code path, then see the Master workbook and its paperback or Kindle option. This is one workbook example, not a service-design approval.
More explained wrong answers: Power factor: the inverted ratio | Ampacity: a skipped factor
What is in the downloadable PDFs?
400 distinct questions with 400 answer explanations in the primary downloadable workbook.
- 4 printable practice exams of 100 questions each in the primary workbook. Earlier diagnostic and mock supplements remain available separately; their repeated questions are not added to the workbook count.
- The 400-question primary-workbook total is separate from the online 368-question bank and online mock forms described on this page. Reused online forms are not added to the unique PDF count.
- Every code question cites NEC 2026; calculation questions show the method. Thirteen electrical-theory calculations have no applicable NEC section. Each printed exam contains 70 scored-style NEC Knowledge questions and 30 Calculations questions; consult the current PSI bulletin for the full official exam, including unscored items.