NEC 314.16 calculates minimum box volume by adding the allowances for conductors, devices, grounding conductors, and applicable internal fittings. Compare that total with the box’s listed volume.
Pass means the listed box volume is at least the calculated requirement.
| Depth (in.) | Volume (in³) | Result |
|---|---|---|
| 1.5 | 7.5 | — |
| 2 | 10 | — |
| 2.25 | 10.5 | — |
| 2.5 | 12.5 | — |
| 2.75 | 14 | — |
| 3.5 | 18 | — |
Worked examples
- Four 12 AWG allowances, internal clamps, one 12 AWG device yoke and three 12 AWG grounds require 18.00 in³.
- Three 14 AWG allowances, a luminaire stud, a hickey, and five entering 14 AWG grounds require 12.50 in³. The fifth ground adds 0.50 in³.
How the calculation works
Add the allowances in NEC 2023 Table 314.16(B) (2023 NEC) by conductor size. Enter conductor allowances after counting long unbroken loops as required by (B)(1) and omitting conductors that originate and terminate inside the box. The tool applies one allowance for internal clamps and one for each support-fitting type present, two per supported device yoke, and a grouped grounding allowance with an extra quarter per entering ground or bonding jumper above four. Use the largest relevant size for each group. Mixed-size devices, multigang devices, isolated grounds, terminal blocks and other box designs need a separate check. Use the box’s marked volume where required.
Frequently asked questions
314.16(B) box fill calculations
Add the applicable volume allowances for conductors, clamps, support fittings, devices and entering equipment grounds. Compare the total with the box’s allowed volume.
Box fill calculation Table
Use Table 314.16(B) (2023 NEC) for the volume per conductor size and Table 314.16(A) for the listed standard metal box volumes, as applicable. Check the marked volume when required.
Do all internal clamps count separately?
No. One or more internal cable clamps together use one allowance based on the largest conductor present.
How does the calculator handle a fifth entering equipment ground?
It adds a quarter allowance for the fifth, based on the largest entering equipment grounding conductor. The first four are covered by one allowance in the supported case.
Related calculators
Worked example
Eight hypothetical allowances at 2 cubic inches each total 16 cubic inches. The per-item values are supplied inputs and do not establish what any actual component counts for.
- List the component categories on paper.
- Add the supplied allowances and compare with the marked box volume in the exercise.
What does this guide cover?
Box fill calculation adds volume allowances for conductors, devices, clamps and grounds and compares the total to the box’s marked volume. Count according to the current NEC rules. Always verify allowances and counting rules in the 2026 NEC. The checklist below shows what to confirm before using this guidance.
Sources for the answer and exercise
Reference edition. The preset code values and cited locators on this page are from the 2023 NEC. Texas adopted the 2026 NEC on September 1, 2026. For Texas work, verify 314.16 and its box and conductor volume tables in the 2026 edition before applying any result. TDLR adoption notice.
Box Fill Calculator
Box fill is the idea that an electrical box must have enough internal volume for the conductors, devices and fittings placed in it, so wires are not crowded and heat can dissipate. Calculators total counted items by volume allowance. Exact allowances come from the adopted code and box markings.
Apply it to a practice example
list items (conductors, devices, clamps, grounds), assign each a volume allowance from the current code, add them, and compare with the box’s marked volume. Hypothetical worked math: if items total 18 cubic inches and the box is marked 20, there is 2 cubic inches of margin. Values here are illustrative.
Sources
- Primary reference (checked November 12, 2026)
- Texas NEC adoption notice (checked November 12, 2026)