A wire-size worksheet separates load current, ampacity, termination ratings and voltage drop. Start with the load and its circuit conditions, then verify the conductor and protection using the adopted edition. An input that passes one check can fail another, so record each check separately before treating a result as a candidate.
The estimate compares the ampacity and voltage-drop minimums among supported copper sizes and returns the larger one.
Preset values are from the 2023 NEC. Check the current adopted edition before use.
Worked examples
- 120 V single phase, 20 A, 150 ft one way, copper, 60 °C and a 3% target gives 6 AWG, limited by voltage drop.
- 480 V three phase, 52 A, 25 ft one way, copper, 75 °C and a 3% target gives 6 AWG, limited by ampacity.
How the calculation works
Use NEC 2023 Table 310.16 in the selected termination column and require conductor insulation rated for at least that temperature. Separately estimate drop with NEC Chapter 9, Table 8 using stranded, uncoated 75 °C copper resistance, one-way length and the single- or three-phase multiplier. The tool assumes 30 °C ambient and three or fewer current-carrying conductors. It does not apply adjustment factors, special load rules, small-conductor protection limits or parallel conductors. Enter the design current required for the load.
Frequently asked questions
What size wire is needed for a 50 amp sub panel?
Check the actual feeder load, conductor material, terminal temperature and voltage drop. The tool compares table ampacity with a drop target. The installation may also require derating or a different sizing rule.
What is the amp rating for number 8 wire?
It depends on the conductor material and temperature column. Use the ampacity chart to look up the base value and check installation limits before using it.
What size wire do I need to run 50 amps 50 ft?
Enter 50 A and a one-way length of 50 ft, then set voltage, phase, material, terminal temperature and the drop limit. Both the ampacity and drop checks must pass for the size shown.
Do I need 6 or 8 gauge wire for 50 amp?
Both the material and the applicable temperature column matter. Compare the base ampacity with the design current and check the length. Apply any installation-specific corrections before selecting the conductor.
Related calculators
Worked example
A 2,400 VA single-phase study load at 120 V draws 20 A. This is the computed load current before any conditions or code-specific sizing steps.
- Divide the apparent power by voltage in the example.
- Keep the result separate from any conductor or breaker selection.
What does this guide cover?
A wire size calculator estimates conductor size from load current, required ampacity, temperature rating and voltage drop. Treat it as a learning aid and confirm final selection against current NEC tables, terminal ratings and local rules. The checklist below shows what to confirm before using this guidance.
Sources for the answer and exercise
Reference edition. The preset code values and cited locators on this page are from the 2023 NEC. Texas adopted the 2026 NEC on September 1, 2026. For Texas work, verify Table 310.16 in the 2026 edition before applying any result. TDLR adoption notice.