Motor loads: output power is not input current

Learning evidence

  1. Viewed
  2. Practiced
  3. Assessment passed
  4. Practical task completed

Join to track your progress

Light it up

view, practice, pass the check, do the task
PackTexas Master Exam Prep
Member toolProgress log — records each of the 4 evidence steps
Next stationHVAC electrical labels: minimum and maximum mean different things →

Electrician helper / apprentice-entry → Journeyman Electrician · 15 skill stations

Identify which motor data are needed to reason about input current.

What you’ll do

  • Your attempt
  • Try a changed case
  • Evidence to prepare
First step

For motor loads, work backward from mechanical output power to input current in a fixed chain. Divide output power by efficiency to get electrical input power. Divide that by power factor to get apparent power. Then divide by the square root of three times the line voltage to reach three-phase line current. Common misconception: mechanical output power equals electrical input power, so current follows directly. Correct practice: efficiency links shaft power to electrical watts, power factor links watts to volt-amperes, and each gets its own step. If a paper case changes the efficiency, power factor or line voltage, keep the chain and recompute only from the changed step downward.

You’re at Level 1. Next: Journeyman Electrician. Membership guides you through it.

You’re at Level 1. Next: Journeyman Electrician. Membership guides you through it.

See membership

Practice for this step: 3 questions

Choose one answer per question. This practice runs in your browser.

A 15-horsepower, 230-volt, three-phase, continuous-duty motor has a table full-load current of 42 amperes. Its nameplate shows a full-load current of 39 amperes and a service factor of 1.15. What are the minimum branch-circuit conductor ampacity and the maximum rating of a separate overload device under the basic overload rule?
A 40-horsepower, 460-volt, three-phase motor (table full-load current 52 A) is supplied by tap conductors 20 feet long from a motor feeder whose conductors are 250 kcmil copper with an ampacity of 255 A. The feeder is protected by a 300-ampere device. For a motor feeder tap not over 25 feet, the tap conductors must have an ampacity of at least one-third of the ampacity of the feeder conductors, and never less than the motor branch-circuit conductors require. Copper ampacities at 75 degrees C: 6 AWG 65 A; 4 AWG 85 A; 3 AWG 100 A; 2 AWG 115 A. What is the smallest tap conductor?
A motor disconnect is required to be in sight from the motor. What does 'in sight from' mean under the NEC?