NEC 408 Panelboards for Apprentices: Circuit Directories, Overcurrent Protection, Backfed Breakers and the High Leg

Updated About 6 min read

Short answer: Article 408 covers switchboards, switchgear and panelboards. The rules apprentices meet most are: every circuit and circuit modification gets a clear, specific entry in the circuit directory (NEC 408.4), each panelboard is protected by an overcurrent device rated no more than the panelboard (NEC 408.36), a backfed plug-in breaker needs an additional fastener, unused openings get closed (NEC 408.7), and on a 4-wire delta the high leg goes on the B phase (NEC 408.3).

PSI lists cabinets and panels among the topics in the Wiring Methods and Materials subject area of the Texas Journeyman exam: 10 scored NEC Knowledge questions and 2 scored Calculations questions. PSI does not say how many cover panelboards alone. The Texas Journeyman Practice Pack has 1,000 original questions and 10 timed mock exams in the real two-part format, with step-by-step solutions for every calculation. Try free practice questions without signing up. Get the full pack for US$39 with one payment.

Tsai Electro is an independent learning site. Not affiliated with TDLR, PSI or NFPA. We explain the ideas in our own words and do not reproduce NEC text. Check every rule and table value in your own 2026 NEC, follow the panel manufacturer’s instructions, and follow your supervisor and the local inspector. Before working inside a panel, follow your employer’s electrical safety program, put the panel in an electrically safe work condition and verify the absence of voltage.

What Article 408 covers

TopicWhere to look
Circuit directory and source marking408.4
Bus and phase arrangement, including the high leg408.3
Unused openings408.7
Panelboard overcurrent protection and backfed devices408.36
Grounding terminals and wire bending spaceArticle 408 and Article 312
Cabinets and the enclosures themselvesArticle 312
Working space in front of the panelSection 110.26

The circuit directory

Every circuit and every circuit modification must be legibly identified on a circuit directory at the panel (NEC 408.4). The description has to be clear and specific enough to tell one circuit from another, and it cannot depend on things that change, such as “Bob’s room” or “spare bedroom” when the room has no fixed name. Installed breakers held for future use are identified as spares.

Useful habits on the job:

  • Write the directory as you terminate, not at the end of the day.
  • Use room names and fixed equipment names, for example “Kitchen counter receptacles, east wall” or “Water heater.”
  • Update the directory whenever you change a circuit, even on service calls.

In other than one- and two-family dwellings, a switchboard, switchgear or panelboard supplied by a feeder is also marked to show where its power comes from. Check the exact wording in your 2026 NEC.

Protecting the panel itself

As a general rule, each panelboard is protected by an overcurrent device rated no more than the panelboard (NEC 408.36). The protection can be a main breaker in the panel or an overcurrent device on the supply side, such as the feeder breaker that supplies it. The section has exceptions, for example for some existing panelboards used as service equipment.

So a 125 A panelboard fed by a 100 A feeder breaker is protected by that breaker. A 100 A panelboard fed by a 125 A feeder breaker is not, unless it has its own main rated 100 A or less.

Backfed breakers and unused openings

  • Backfed plug-in breakers. When a plug-in breaker is backfed and terminates field-installed supply conductors, for example as the main in some panels or for a generator connection, it must be secured with an additional fastener that takes more than a pull to release (NEC 408.36). Use the hold-down kit the panel manufacturer lists.
  • Unused openings. Unused openings for circuit breakers and switches must be closed with identified closures or other approved means that give protection substantially equivalent to the wall of the enclosure (NEC 408.7). Use the manufacturer’s filler plates, not tape or cardboard.

The high leg on a 4-wire delta

On a 120/240 V three-phase 4-wire delta system, one phase measures about 208 V to the neutral. That phase is called the high leg, or wild leg. It is not suitable for 120 V loads.

  • Location. In a panelboard, the high leg is generally connected to the B phase (NEC 408.3). The section has an exception for equipment in the same section as the metering equipment, which may follow the meter’s phase arrangement. Check it before you apply the B-phase rule.
  • Marking. The high leg conductor is identified by an outer finish orange in color, or by other effective means, wherever a connection is made and the neutral is also present. The marking rule is in Article 110.
  • Danger. If a single-pole breaker for a 120 V load is snapped onto the high leg, the load sees about 208 V.

Worked example: why the high leg reads about 208 V

A 120/240 V three-phase 4-wire delta is center-tapped on one winding. The neutral sits at the midpoint of that 240 V winding. Find the voltage from the high leg to the neutral.

  1. The three corners of the delta form an equilateral triangle with 240 V sides.
  2. The neutral is at the midpoint of one side, so it is 120 V from each of the two corners on that side.
  3. The high leg is the opposite corner. The distance from a corner of an equilateral triangle to the midpoint of the opposite side is the side × 0.866.
  4. 240 V × 0.866 = 207.8 V, about 208 V.
  5. Check. 120² + 207.8² = 14,400 + 43,181 = 57,581. The square root is about 240, the line-to-line voltage, which matches the right triangle formed by the high leg, the neutral and one corner.

Check yourself

  1. Can a circuit directory entry say “Bob’s room”? No. It must be clear and specific and not depend on changing conditions.
  2. A 100 A panelboard is fed from a 125 A feeder breaker and has no main. Is it protected? No. The protection must not exceed the panelboard rating.
  3. On a 120/240 V 4-wire delta, which phase is generally the high leg in a panelboard? The B phase.

Disclosure: If you buy through the Amazon link below, Tsai Electro may earn a commission at no extra cost to you. As an Amazon Associate I earn from qualifying purchases.

Find Articles 408 and 110 faster on exam day

NFPA 70, National Electrical Code, 2026 Edition (softcover). Highlight the directory, panel protection and high leg rules in 408 and the high leg marking and working space rules in 110, since panel questions often send you to both. The Texas exam is open book. PSI allows a soft-bound NEC with highlighting, underlining and notes made in advance. Loose-leaf, spiral-bound and ring-bound copies are not allowed, and only permanent index tabs made or supplied by the NEC publisher are permitted; homemade and third-party tabs are not.

FAQ

What does the NEC require on a panel directory?

Every circuit and circuit modification must be legibly identified with a clear and specific description, at the panel. Descriptions cannot depend on changing conditions, and spares are identified as spares.

Does a backfed breaker need a hold-down?

Yes, when it is backfed and terminates field-installed supply conductors. It must be secured with an additional fastener that requires more than a pull to release. Use the kit the panel manufacturer lists.

Which phase is the high leg in a panel?

On a 120/240 V 4-wire delta, the high leg is generally connected to the B phase in a panelboard, and it is marked orange or by other effective means. It measures about 208 V to the neutral.

Are panelboards on the Texas Journeyman exam?

Yes. PSI lists cabinets and panels in the Wiring Methods and Materials subject area, which has 10 scored NEC Knowledge questions and 2 scored Calculations questions. PSI does not say how many cover panelboards alone.

Next step: practice panel and wiring method questions under timed exam conditions. The Texas Journeyman Practice Pack has 10 timed mock exams in the two-part format, 59 questions in 130 minutes and 26 in 110 minutes, with step-by-step solutions for every calculation. 1,000 questions, free questions to try first with no sign-up, US$39, one payment.

Next skill: services and overcurrent protection. Panels sit downstream of the service and the breakers that protect them: NEC 230 and 240 services and overcurrent protection.

Sources checked October 2026