Short answer: For an air conditioner, size the conductors from the nameplate MCA (minimum circuit ampacity) and pick a breaker no larger than the nameplate MOCP (maximum overcurrent protection). For a storage water heater of 120 gallons or less, the branch circuit is rated at least 125% of the nameplate current. A/C equipment generally needs a disconnecting means within sight of the unit and readily accessible from it. Appliances also need a disconnecting means, and the permitted method depends on the appliance: a cord and plug, a local disconnect, or a breaker that can be locked open, where the rule allows it.
HVAC and appliances are covered under Electrical Equipment and Devices in both parts of the Texas Journeyman exam. The NEC Knowledge part has 59 questions in 130 minutes, and the Calculations part has 26 questions in 110 minutes. The Texas Journeyman Practice Pack has 1,000 original questions and 10 timed mock exams in the real two-part format, with step-by-step solutions for every calculation. Try free practice questions without signing up. Get the full pack for US$39 with one payment.
Tsai Electro is an independent learning site. Not affiliated with TDLR, PSI or NFPA. We explain the ideas in our own words and do not reproduce NEC text. Check every rule and table value in your own 2026 NEC, and follow the equipment nameplate and installation instructions.
Which article applies
| Equipment | Article | What sizes the circuit |
|---|---|---|
| Air conditioner or heat pump with a hermetic compressor | 440 | Nameplate MCA and MOCP |
| Fixed storage water heaters, dishwashers, disposers, ranges and cooktops | 422, plus other articles that apply | Equipment rating and the branch-circuit rules that apply; the 125% continuous-load treatment covers qualifying storage water heaters, not every appliance |
| Baseboard heaters and other fixed space heating | 424 | Nameplate rating at 125% |
| Motors covered by Article 430, including many standalone motors (equipment-specific rules may also apply) | 430 | NEC table full-load current for most conductor and short-circuit protection sizing; nameplate current for overload protection |
The last row is the classic trap. A separately installed pool pump motor is a typical Article 430 motor. A blower motor inside listed furnace equipment can also fall under appliance and equipment rules, so do not size the whole furnace by Article 430 alone. A sealed compressor in a condensing unit is under Article 440 and uses its own nameplate numbers.
Air conditioners: MCA and MOCP
For a listed condensing unit, the manufacturer gives you two nameplate numbers that make branch-circuit sizing simpler. You still check conductor ampacity after any adjustment and correction factors, terminal temperature limits and the installation instructions.
- MCA (minimum circuit ampacity). Select conductors with enough ampacity to meet the marked MCA after applicable adjustment and correction factors. Separately verify that the conductor size satisfies the equipment’s terminal temperature limitations. Both checks must pass. MCA is a sizing minimum, not the running current of the unit.
- MOCP (maximum overcurrent protection). This is the upper limit for the breaker or fuse, not automatically the size you must use. Some nameplates say the fuse must be a time-delay type, or HACR breaker; follow it.
A hermetic compressor draws a high starting current, and Article 440 has its own short-circuit and ground-fault protection rules for it, so the breaker can be larger than the usual limit for small conductors (NEC 240.4(G)). The conductors still have to meet the MCA, and the short-circuit and ground-fault protective device has to follow Article 440 and cannot exceed the nameplate maximum. Unlike the water heater example below, a qualifying motor-compressor circuit can have short-circuit and ground-fault protection rated above the conductor ampacity when Article 440 permits it. That does not remove the MCA, the equipment markings or the other conductor protection rules. That is why a nameplate may allow a 35 A breaker on a circuit whose MCA is about 21 A.
The disconnect must generally be within sight of the unit and readily accessible (NEC 440.14). Within sight means visible and no more than 50 ft away. Section 440.14 has limited exceptions, including certain industrial installations and certain cord-and-plug-connected equipment, so confirm the exact condition that applies before you decide where the disconnect goes. It may be mounted on or within the unit, but not on a panel designed to give access to the equipment and not where it hides the equipment nameplate. Working space rules still apply.
Appliances: the 125% loads
- Storage water heaters. A fixed storage-type water heater of 120 gallons or less is treated as a continuous load (NEC 422.13). Size the branch-circuit conductors and overcurrent protection at least 125% of the nameplate current, and count the load as continuous in feeder calculations too.
- Fixed space heating. Fixed electric space-heating equipment is treated as a continuous load, so its branch-circuit conductors and overcurrent protection are sized at 125% of the load, within the equipment ratings.
- Disconnects. Every appliance needs a disconnecting means, and the allowed method depends on the appliance and the installation (NEC 422.31). For a permanently connected appliance such as a water heater, check the Article 422 rules to see whether you need a disconnect within sight or whether a breaker that can be locked in the open position is allowed. For a cord-and-plug-connected appliance, the plug can serve as the disconnect where the conditions are met. Do not assume an ordinary breaker out of sight satisfies the rule.
- Cord-and-plug appliances. Cord-and-plug-connected dishwashers and food waste disposers have equipment-specific installation requirements (NEC 422.16(B)). Check the applicable NEC provisions and manufacturer instructions for permitted cord lengths, receptacle locations and disconnecting means.
Worked example 1: a 4,500 W water heater
A 4,500 W, 240 V storage water heater, 50 gallons.
- Nameplate current: 4,500 ÷ 240 = 18.75 A.
- Circuit rating at 125%: 18.75 × 1.25 = 23.4375 A, about 23.44 A.
- The calculated minimum overcurrent device rating is 23.44 A. A 25 A breaker is the smallest standard rating that meets the 23.44 A minimum, provided it also complies with the water heater markings and any maximum overcurrent rating that applies under Article 422. The conductor ampacity must also be at least 23.44 A. At the usual 60°C terminal rating, 12 AWG copper has a 20 A ampacity, which is below 23.44 A, so it does not work here. 10 AWG copper, 30 A in the 60°C column, is the usual choice. Check terminal ratings, conductor type and any adjustment or correction factors.
Check it another way: 4,500 × 1.25 = 5,625 W, and 5,625 ÷ 240 = 23.4375 A. Both methods give a minimum of 23.44 A. A 25 A standard breaker meets that minimum. The 125% figure sets the minimum rating only; the conductor is still checked on its own, as in step 3, along with the equipment ratings and terminal limits.
Worked example 2: a condensing unit
The nameplate reads MCA 21.3 A and MOCP 35 A.
- Conductor: allowable ampacity at least 21.3 A. Assuming copper conductors, 60 °C terminals and no adjustment or correction factors, 10 AWG copper (30 A in the 60 °C column) covers the 21.3 A MCA.
- Overcurrent protection: the nameplate MOCP of 35 A is the upper limit. A 35 A breaker does not exceed the nameplate MOCP. It is acceptable only if circuit-breaker protection is permitted by the equipment marking and the applicable Article 440 requirements. If the equipment requires fuses, use the specified fuse type. The breaker must also follow the manufacturer’s instructions, and a smaller one may trip on compressor starting current.
- Sizing check: under the stated assumptions, the 30 A conductor ampacity exceeds the 21.3 A MCA, and the 35 A breaker does not exceed the 35 A MOCP. These two numerical checks pass, but the breaker is permitted only if the equipment markings and applicable Article 440 requirements allow circuit-breaker protection. Final compliance still depends on adjustment and correction factors, terminal ratings, equipment markings and the installation instructions.
If the nameplate said MOCP 30 A, a 35 A breaker would fail inspection even though the wire is the same.
Check yourself
- Which nameplate number sets the largest breaker for an A/C unit? MOCP.
- A 4,500 W, 240 V fixed storage water heater of 120 gallons or less: what minimum circuit rating? 18.75 A × 125% = 23.44 A. The smallest standard breaker that meets it is 25 A, subject to the equipment markings.
- Is a furnace blower motor sized under Article 440? No. A furnace blower is not a hermetic refrigerant motor-compressor. Article 440 covers air-conditioning and refrigerating equipment that has those compressors. Article 430 may apply to the blower motor, but the complete furnace circuit is checked under the equipment and appliance rules that apply, the furnace nameplate and the installation instructions.
Disclosure: If you buy through the Amazon link below, Tsai Electro may earn a commission at no extra cost to you. As an Amazon Associate I earn from qualifying purchases.
Formulas for the calculation part
Ugly’s Electrical References, 2026 Edition. A pocket reference for practicing calculations and checking formulas, ampacity information, conversions and motor data. Use it next to your NEC while you study or work in the field. It is spiral-bound and is not an approved reference for the Texas Journeyman exam, so do not plan on bringing it into the exam room.
FAQ
What do MCA and MOCP mean on an air conditioner?
MCA is minimum circuit ampacity: the conductors must carry at least this current. MOCP is maximum overcurrent protection: the breaker or fuse must not be larger than this value.
Why is a water heater circuit sized at 125%?
The NEC treats a storage water heater of 120 gallons or less as a continuous load, so its branch circuit must be rated at least 125% of the nameplate current.
Can the A/C breaker be bigger than the wire’s ampacity?
Yes, for a qualifying motor-compressor circuit under Article 440. Article 440 can permit a compressor circuit’s short-circuit and ground-fault protective device to have a rating higher than the conductor ampacity. The conductors must meet the MCA, and the protective device must comply with Article 440, the nameplate MOCP and the equipment instructions. This does not apply to ordinary circuits.
Are HVAC questions on the Texas Journeyman exam?
Yes. PSI lists air conditioning, refrigeration and heating equipment and appliances under Electrical Equipment and Devices. That subject area has 10 scored NEC Knowledge questions and 2 scored Calculations questions. Those totals cover the whole area; PSI does not break out a separate count for HVAC and appliances.
Sources checked October 2026
- PSI Candidate Information Bulletin, Texas electrician examinations (updated September 15, 2026): https://test-takers.psiexams.com/api/content/bulletin/1682
- NFPA 70, National Electrical Code, 2026 Edition, Articles 240, 422, 424, 430 and 440